Remote bus cable

By meters, Cable for remote bus, INTERBUS, shielded, PVC, May green RAL 6017, 6-conductors (3 x 2 x 0.22 mm²), color single conductors: green-yellow, white-brown, gray-pink, fixed arrangement

More details


Cables > Data and communication cable

Industrial Field Connectivity (IFC)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total: $6.11
Unit price: $6.11/m
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Often bought together

Best sellers

More info



Key Commercial Data

Orderkey2806286
Packing unit1 M
NoteMade to Order (non-returnable)
Catalog pagePage 333 (C-8-2013)
GTIN4017918074791
Weight per Piece (excluding packing)70.160 g
Custom tariff number85444993
Country of originDE (Germany)

General data

Number of positions6
Alternative short product descriptionRemote bus cable

Cable

Signal type/categoryINTERBUS
Cable structure3 x 2 x 0.22 mm²
Conductor cross section3x 2x 0.22 mm²
Conductor structure signal line7x 0.20 mm
Wire colorsGreen-yellow, white-brown, gray-pink
Twisted pairs2 cores to the pair
Overall twist3 pairs to the core
ShieldingBraided copper wires
External sheath, colormay green RAL 6017
External cable diameter D7 mm
Minimum bending radius, fixed installation7.5 x D
Minimum bending radius, flexible installation15 x D
Outer sheath, materialPVC
Material conductor insulationPE
Conductor materialBare Cu litz wires
Insulation resistance≥ 5 GΩ*km
Loop resistance≤ 186.00 Ω/km
Cable capacity≤ 60 nF/km (At 800 Hz)
Wave impedance120 Ω ±20 % (at 64 kHz)
100 Ω ±15 % (with 1 MHz)
Near end crosstalk attenuation (NEXT)≥ 61 dB (at 772 kHz)
≥ 59 dB (with 1 MHz)
≥ 55 dB (at 2 МHz)
≥ 50 dB (at 4 МHz)
≥ 46 dB (at 8 МHz)
≥ 44 dB (at 10 MHz)
≥ 41 dB (at 16 MHz)
≥ 40 dB (at 20 МHz)
Attenuation≤ 15 dB/km (at 256 kHz)
≤ 24 dB/km (at 772 kHz)
≤ 27 dB/km (with 1 MHz)
≤ 52 dB/km (at 4 МHz)
≤ 84 dB/km (at 10 MHz)
≤ 112 dB/km (at 16 MHz)
≤ 119 dB/km (at 20 МHz)
Signal speed0.66 c
Coupling resistance< 250.00 mΩ/m (at 30 MHz)
Nominal voltage, cable250 V (Peak value, not for high-power applications)
Test voltage Core/Core1500 Vrms
Test voltage Core/Shield1000 Vrms
Flame resistanceaccording to VDE 0472, Part 4, test type B
according to IEC 60332-1
Ambient temperature (operation)-30 °C ... 70 °C (cable, fixed installation)
-5 °C ... 70 °C (cable, flexible installation)

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


ETIM for 2806286 Cable (EC003249)
Feature Name Feature Value
Conductor surface (EF010804) Other
Nominal cross section conductor (EF000060) 0.22 mm²
Conductor category (EF001632) Class 2 = stranded
Number of cores (EF001792) 6
Material core insulation (EF000061) Other
Specification core insulation (EF011805) Polyethylene (PE)
Core identification (EF000067) Other
Screen over stranding element (EF001623) Braiding
Stranding (EF003802) Other
Longitudinal water blocking cable (EF011011) No
Radial water blocking cable (EF011012) No
Suitable for underground installation (EF003689) No
Protective sheath (EF001691) None
Material outer sheath (EF001625) Polyvinyl chloride (PVC)
Specification material outer sheath (EF011806) Other
Colour outer sheath (EF001618) Other
Low smoke according to EN IEC 61034-2 (EF003799) No
Oil resistant according to EN IEC 60811-404 (EF009770) No
Outer diameter approx. (EF003921) 7 mm
Min. permitted bending radius, moving application/free movement (EF011802) 105 mm
Min. permitted bending radius, stationary application/permanent installation (EF011803) 53 mm
Permitted cable outer temperature during assembling/handling (EF001685) -5 °C
Permitted cable outer temperature after assembling without vibration (EF001686) -30 °C
Category (EF001619) Other

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.