PT 2-PE/S- 24AC-ST 2839318 PHOENIX CONTACT Protective plug PT with surge voltage equipment protection for po.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PT 2-PE/S- 24AC-ST 2839318 PHOENIX CONTACT Protective plug PT with surge voltage equipment protection for po..

PT 2-PE/S- 24AC-ST

2839318

PHOENIX_CONTACT

10

Protective plug PT with surge voltage equipment protection for power supply units, visual fault warning. Nominal voltage: 24 V AC

More details


Home > PHOENIX CONTACT

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Technical data

Notes
Notes on operationNot suitable for systems with grounded positive pole

Product properties
Product typeDevice protection
IEC power supply systemTT
TN-S
TypeMale
Number of positions2
Surge protection fault messageoptical
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.00
IEC test classificationIII
T3
EN typeT3

Dimensions
Dimensional drawingzlsstgybwl.jpg
Width17.7 mm
Height45 mm
Depth52 mm
Horizontal pitch1 Div.
Complete module width17.7 mm
Complete module height90 mm
Complete module depth65.5 mm

Material specifications
Flammability rating according to UL 94V0
Housing materialPA 6.6

Protective circuit
Direction of action1L-N & N-PE
Nominal frequency fN50 Hz
60 Hz
Maximum continuous voltage UC34 V AC
44 V DC
Rated load current IL26 A (30 °C)
Residual current IPE≤ 1 µA
Standby power consumption PC≤ 60 mVA
Operating effective current ICat UC≤ 1.5 mA
Nominal discharge current In(8/20) µs1 kA
Voltage protection level Up(L-N)≤ 180 V
Voltage protection level Up(L-PE)≤ 550 V
Voltage protection level Up(N-PE)≤ 550 V
Residual voltage at In≤ 180 V
≤ 120 V
≤ 120 V
Response time tA(L-N)≤ 25 ns
Response time tA(L-PE)≤ 100 ns
Response time tA(N-PE)≤ 100 ns
Max. required back-up fuse25 A (gL)
25 A (MCB 25 A B/C)
Short-circuit withstand capability IPwith max. backup fuse (r.m.s.)1.5 kA

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 85 °C (non-Ex)
-40 °C ... 80 °C (Class I Div. 2 Gr. A, B, C, D)

Standards and regulations
Air clearances and creepage distances
Standards/regulationsDIN VDE 0110-1 / IEC 60664-1
Standards
Standards/regulationsIEC 61643-1
EN 61643-11/A11
UL 1449
Standards/specificationsIEC 61643-1
Note2005
Standards/specificationsEN 61643-11/A11
Note2007
Standards/specificationsUL 1449
Noteed. 2

Mounting
Mounting typeon base element

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.