PT 2X1VA-230AC-ST 2839198 PHOENIX CONTACT Surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PT 2X1VA-230AC-ST 2839198 PHOENIX CONTACT Surge protection plug

PT 2X1VA-230AC-ST

2839198

PHOENIX_CONTACT

Surge protection plug

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $137.44
Unit price: $137.44

Quantity Price
1+$137.44
2+$116.72
3+$108.15
4+$105.38
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2839198
Packing unit10 pc
Catalog pagePage 114 (C-4-2017)
GTIN4017918182854
Weight per Piece (excluding packing)24.230 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height44.8 mm
Width17.5 mm
Depth51.7 mm
Horizontal pitch1 Div.
Complete module height90 mm
Complete module width17.7 mm
Complete module depth65.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorjet black RAL 9005
Mounting typeon base element
TypeMale
Direction of actionLine-Line & Line-Earth Ground
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.00

Additional descriptions

NoteTechnical data is valid in association with the following specified base elements:
PT -BE/ FM 2839282

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN230 V AC (50/60 Hz)
Maximum continuous voltage UC275 V DC
275 V AC (50/60 Hz)
Rated current26 A AC (30 °C)
1 A DC (82 °C)
Operating effective current ICat UC≤ 1.5 mA AC
≤ 2 mA DC
Residual current IPE≤ 3 mA AC
≤ 4 mA DC
Nominal discharge current In(8/20) µs (line-earth)2.5 kA
Pulse discharge current Iimp(10/350) µs500 A
Total discharge current Itotal(8/20) µs5 kA
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 650 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 650 V
Voltage protection level Up(line-earth)≤ 750 V (C1 - 1.4 kV / 0.7 kA)
≤ 900 V (C2 - 5 kV/2,5 kA)
≤ 750 V (C3 - 100 A)
Response time tA(line-earth)≤ 25 ns
Input attenuation aE, asym.typ. 0.3 dB (≤ 650 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm systemtyp. 2.2 MHz
Capacity (line-earth)typ. 1 nF
Surge protection fault messagenone
Max. required back-up fuse25 A AC (gL/gG)
1 A DC (T)
Impulse durability (line-earth)C1 - 1,4 kV / 0,7 kA
C2 - 5 kV/2.5 kA
C3 - 100 A
D1 - 500 A

Connection data

Connection methodScrew connection (in connection with the base element)
Screw threadM3
Tightening torque0.5 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Standards and Regulations

Standards/specificationsIEC 61643 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21 2001 + A1:2009 + A2:2013

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.