Product successfully added to your shopping cart
EMD-FL-V-300
2866048
PHOENIX_CONTACT
1
Monitoring relay
Supervisory relay for 1-phase voltage monitoring of 0...300 V AC/DC, overvoltage/undervoltage or Window, error memory, long-range power supply, 2 switched contacts
Monitoring relay for monitoring 1-phase voltages of 0…300 V AC/DC, overvoltage/undervoltage or window, error memory, wide range power supply unit, 2 changeover contacts
Relays > Voltage monitoring relay
Industrial Relays
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| Product type | Voltage monitoring relay |
| Operating mode | 100% operating factor |
| Mechanical service life | approx. 2x 107cycles |
| Data management status | |
| Article revision | 03 |
| Insulation characteristics | |
| Insulation | Basic insulation |
| Overvoltage category | III |
| Pollution degree | 2 |
| Service life electrical | 2x 105cycles at ohmic load, 1000 VA |
| Maximum power dissipation for nominal condition | 1 W |
| Mains type | 1-phase |
| Rated insulation voltage | 300 V |
| Rated surge voltage | 4 kV |
| Supply | |
| Supply voltage range | 24 V AC ... 240 V AC -15 % ... +10 % |
| 24 V DC ... 240 V DC -20 % ... +25 % | |
| Type of supply voltage | AC/DC |
| Nominal power consumption | 4.5 VA (1.5 W) |
| Input name | Measuring input |
| Measured value | DC, AC sine |
| Protection | ≤ 20 A |
| Input voltage range | 0 V ... 30 V AC/DC (connection terminal blocks: U1 and GND) |
| 0 V ... 60 V AC/DC (connection terminal blocks: U2 and GND) | |
| 0 V ... 300 V AC/DC (connection terminal blocks: U3 and GND) | |
| Maximum input voltage | 100 Vrms(connection terminal blocks: U1 and GND) |
| 150 Vrms(connection terminal blocks: U2 and GND) | |
| 440 Vrms(connection terminal blocks: U3 and GND) | |
| Input resistance of voltage input | 47 kΩ (connection terminal blocks: U1 and GND) |
| 100 kΩ (connection terminal blocks: U2 and GND) | |
| 470 kΩ (connection terminal blocks: U3 and GND) | |
| Frequency range | 48 Hz ... 400 Hz |
| Maximum temperature coefficient | < 0.1 %/K |
| Setting range for response delay | 0.1 s ... 10 s |
| Setting range for starting delay | 0 s ... 10 s |
| Min. setting range | 5 % ... 95 % (From UN) |
| Max. setting range | 10 % ... 100 % (From UN) |
| Function | Undervoltage |
| Overvoltage | |
| Window | |
| Error memory | |
| Basic accuracy | ± 5 % (of scale end value) |
| Setting accuracy | ≤ 5 % (of scale end value) |
| Repeat accuracy | ≤ 2 % |
| Recovery time | 500 ms |
| Switching | |
| Contact switching type | 2 floating changeover contacts |
| Maximum switching voltage | 250 V AC (in acc. with IEC 60664-1) |
| Interrupting rating (ohmic load) max. | 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing) |
| 1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing) | |
| Output fuse | 5 A (fast-blow) |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Conductor cross section rigid | 0.5 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.25 mm² ... 2.5 mm² |
| Conductor cross section AWG | 20 ... 14 |
| Width | 22.5 mm |
| Height | 90 mm |
| Depth | 113 mm |
| Color | green (RAL 6021) |
| Housing insulation material | Polyamide PA, self-extinguishing |
| Ambient conditions | |
| Degree of protection (Housing) | IP40 (Housing) |
| Degree of protection (Connection terminal blocks) | IP20 (Connection terminal blocks) |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| -25 °C ... 40 °C (corresponds to UL 508) | |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Permissible humidity (operation) | 15 % ... 85 % |
| CE | |
| Certificate | CE-compliant |
| UL, USA/Canada | |
| Identification | UL/C-UL Listed UL 508 |
| Electromagnetic compatibility | Conformance with EMC directive |
| Low Voltage Directive | Conformance with Low Voltage Directive |
| Noise immunity | EN 61000-6-2 |
| Noise emission | EN 61000-6-4 |
| Standards/regulations | EN 50178 |
| Mounting type | DIN rail mounting |
| Assembly note | on standard DIN rail NS 35 in accordance with EN 60715 |
| Mounting position | any |
| Feature Name | Feature Value |
|---|---|
| Type of electric connection (EF003961) | Screw connection |
| With detachable clamps (EF003340) | No |
| Type of voltage measuring range (EF003399) | AC/DC |
| Response value voltage (EF008193) | 0 V |
| Single-phase under voltage possible (EF003390) | Yes |
| Three-phase under voltage possible (EF003391) | No |
| Single-phase over voltage possible (EF003392) | Yes |
| Three-phase over voltage possible (EF003393) | No |
| Single-phase hysteresis possible (EF003394) | Yes |
| Three-phase hysteresis possible (EF003395) | No |
| Contains function DC-under voltage (EF003396) | No |
| Contains function DC-over voltage (EF003397) | No |
| Contains function DC-voltage hysteresis (EF003398) | No |
| Number of contacts as normally closed contact (EF008255) | 0 |
| Number of contacts as normally open contact (EF008256) | 0 |
| Number of contacts as change-over contact (EF008257) | 2 |
| Width (EF000008) | 22.5 mm |
| Height (EF000040) | 90 mm |
| Depth (EF000049) | 113 mm |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOG PHOENIX INTERFACE TECHNOLOGY AND SWITCHING DEVICES EN .pdf | 28 Mbytes |
|
| PHOENIX CONTACT-2866048-EMD-FL-V-300 | 113 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.