Monitoring relay for 1-phase current monitoring from 0...10 A AC/DC, overcurrent/minimum current or Window, error memory, long-range power supply, 2 switched contacts

Monitoring relay for monitoring 1-phase currents of 0 … 10 A AC/DC, overcurrent/undercurrent or window, error memory, wide range power supply unit, 2 changeover contacts

More details


Relays > Current monitoring relay

Industrial Relays

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total: $301.28
Unit price: $301.28
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Technical data

Notes
Utilization restriction
EMC noteEMC: class A product, see manufacturer's declaration in the download area

Product properties
Product typeCurrent monitoring relay
Operating mode100% operating factor
Mechanical service lifeapprox. 2x 107cycles
Data management status
Article revision03
Insulation characteristics
InsulationBasic insulation
Overvoltage categoryIII
Pollution degree2

Electrical properties
Service life electrical2x 105cycles at ohmic load, 1000 VA
Maximum power dissipation for nominal condition1 W
Mains type1-phase
Rated insulation voltage300 V
Rated surge voltage4 kV
Supply
Supply voltage range24 V AC ... 240 V AC -15 % ... +10 %
24 V DC ... 240 V DC -20 % ... +25 %
Nominal power consumption4.5 VA (1.5 W)

Input data
Input nameMeasuring input
Measured valueDC, AC sine
Input current range0 mA ... 100 mA (Connection terminals: I1 and GND)
0 A ... 1 A (Connection terminals: I2 and GND)
0 A ... 10 A (Connection terminals: I3 and GND)
Overload capacity800 mA (at IN= 100 mA)
3 A (at IN= 1 A)
12 A (at IN= 10 A)
Input resistance current input470 mΩ (at IN= 100 mA)
47 mΩ (at IN= 1 A)
5 mΩ (at IN= 10 A)
Frequency range48 Hz ... 400 Hz
Maximum temperature coefficient< 0.1 %/K
Setting range for response delay0.1 s ... 10 s
Setting range for starting delay0 s ... 10 s
Min. setting range5 % ... 95 % (from IN)
Max. setting range10 % ... 100 % (from IN)
FunctionOvercurrent
Undercurrent
Window
Error memory
Basic accuracy± 5 % (of scale end value)
Setting accuracy≤ 5 % (of scale end value)
Repeat accuracy≤ 2 %
Recovery time500 ms

Output data
Switching
Contact switching type2 floating changeover contacts
Maximum switching voltage250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max.750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse5 A (fast-blow)

Connection data
Connection methodScrew connection
Stripping length8 mm
Conductor cross section rigid0.5 mm² ... 2.5 mm²
Conductor cross section flexible0.25 mm² ... 2.5 mm²
Conductor cross section AWG20 ... 14

Dimensions
Width22.5 mm
Height90 mm
Depth113 mm

Material specifications
Colorgreen (RAL 6021)
Housing insulation materialPolyamide PA, self-extinguishing

Environmental and real-life conditions
Ambient conditions
Degree of protection (Housing)IP40 (Housing)
Degree of protection (Connection terminal blocks)IP20 (Connection terminal blocks)
Ambient temperature (operation)-25 °C ... 55 °C
-25 °C ... 40 °C (corresponds to UL 508)
Ambient temperature (storage/transport)-25 °C ... 70 °C
Climatic class3K3 (in acc. with EN 60721)
Permissible humidity (operation)15 % ... 85 %

Approvals
CE
CertificateCE-compliant
UL, USA/Canada
IdentificationUL/C-UL Listed UL 508

EMC data
Electromagnetic compatibilityConformance with EMC directive
Low Voltage DirectiveConformance with Low Voltage Directive
Noise immunityEN 61000-6-2
Noise emissionEN 61000-6-4

Standards and regulations
Standards/regulationsEN 50178

Mounting
Mounting typeDIN rail mounting
Assembly noteon standard DIN rail NS 35 in accordance with EN 60715
Mounting positionany

ETIM for 2866022 Relays (EC001440)
Feature Name Feature Value
Type of electric connection (EF003961) Screw connection
With detachable clamps (EF003340) No
Current measuring range (EF000417) 0 A
Single-phase under current possible (EF003405) Yes
Three-phase under current possible (EF003406) No
Single-phase overcurrent possible (EF003407) Yes
Three-phase overcurrent possible (EF003408) No
Single-phase hysteresis possible (EF003394) Yes
Three-phase hysteresis possible (EF003395) No
Contains function DC-voltage under current (EF003409) Yes
Contains function DC-voltage overcurrent (EF003410) Yes
Function DC-current hysteresis (EF003411) Yes
External current transformer (EF001923) No
Number of contacts as normally closed contact (EF008255) 0
Number of contacts as normally open contact (EF008256) 0
Number of contacts as change-over contact (EF008257) 2
Width (EF000008) 22.5 mm
Height (EF000040) 90 mm
Depth (EF000049) 113 mm

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.