PHOENIX CONTACT  EMD-FL-3V-690 2885249 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

EMD-FL-3V-690 2885249 PHOENIX CONTACT Monitoring relay

Reference: EMD-FL-3V-690

Code: 2885249

Manufacturer: PHOENIX CONTACT

Description:

Monitoring relay
Supervisory relay for 3-phase voltage monitoring of 483...897 V AC, undervoltage, Window, phase sequence, phase fault, asymmetry, selectable supply voltage via power module, 2 switched contacts

Categories:

  • Relays > Voltage monitoring relay
  • PHOENIX CONTACT > Industrial Relays

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • ETIM
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 384,12 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

Key Commercial Data

Orderkey2885249
Packing unit1 pc
Catalog pagePage 268 (C-5-2017)
GTIN4017918996482
Weight per Piece (excluding packing)277.100 g
Custom tariff number85364900
Country of originAT (Austria)

Dimensions

Width45 mm
Height90 mm
Depth113 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 55 °C
-25 °C ... 40 °C (corresponds to UL 508)
Ambient temperature (storage/transport)-25 °C ... 70 °C

Input data

Nominal input voltage UN3 ~ 690 V
Maximum temperature coefficient< 0.1 %/K
FunctionUndervoltage, window, asymmetry, phase sequence, phase failure
Min. setting range-30 % ... 20 % (From UN)
Max. setting range-20 % ... 30 % (From UN)
Min setting range of the voltage threshold value483 V AC ... 828 V AC
Max. setting range of the voltage threshold value552 V AC ... 897 V AC
Setting range for response delay0.1 s ... 10 s
Basic accuracy± 5 % (of scale end value)
Setting accuracy≤ 5 % (of scale end value)
Repeat accuracy≤ 2 %
Asymmetry5 % ... 25% / OFF
Recovery time500 ms

Contact side

Contact type2 floating PDT contacts
Maximum switching voltage250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max.750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse5 A (fast-blow)

Power supply

Supply voltage range230 V AC ... 500 V AC (see Power modules)

General

Mechanical service lifeapprox. 2x 107cycles
Operating mode100% operating factor
Mounting positionany
Assembly instructionson standard DIN rail NS 35 in accordance with EN 60715
Electromagnetic compatibilityConformance with EMC Directive 2004/108/EC
Overvoltage categoryIII, basic insulation (as per EN 50178)
Housing insulation materialPolyamide PA, self-extinguishing
Colorgreen
Rated insulation voltage600 V (acc. to EN 50178)
ConformanceCE-compliant
UL, USA/CanadaUL/C-UL listed UL 508

Connection data

Conductor cross section flexible min.0.25 mm²
Conductor cross section flexible max.2.5 mm²
Connection methodScrew connection
Stripping length8 mm
Conductor cross section solid0.5 mm² ... 2.5 mm²
Conductor cross section flexible0.25 mm² ... 2.5 mm²
Conductor cross section AWG20 ... 14
Tightening torque1 Nm

Standards and Regulations

Electromagnetic compatibilityConformance with EMC Directive 2004/108/EC
Noise emissionEN 61000-6-3
Noise immunityEN 61000-6-2
Low Voltage DirectiveConformance with LV directive 2006/95/EC
ConformanceCE-compliant
UL, USA/CanadaUL/C-UL listed UL 508

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications

ETIM for 2885249 Relays (EC001438)

Feature nameType of electric connection (EF003961)
Feature valueScrew connection
Feature nameWith detachable clamps (EF003340)
Feature valueNo
Feature nameVoltage measuring range 1 (EF006134)
Feature value483 V
Feature nameType of voltage measuring range (EF003399)
Feature valueAC
Feature nameSingle-phase under voltage possible (EF003390)
Feature valueNo
Feature nameThree-phase under voltage possible (EF003391)
Feature valueYes
Feature nameSingle-phase over voltage possible (EF003392)
Feature valueNo
Feature nameThree-phase over voltage possible (EF003393)
Feature valueNo
Feature nameSingle-phase hysteresis possible (EF003394)
Feature valueNo
Feature nameThree-phase hysteresis possible (EF003395)
Feature valueYes
Feature nameContains function DC-under voltage (EF003396)
Feature valueNo
Feature nameContains function DC-over voltage (EF003397)
Feature valueNo
Feature nameContains function DC-voltage hysteresis (EF003398)
Feature valueNo
Feature nameNumber of contacts as normally closed contact (EF008255)
Feature value0
Feature nameNumber of contacts as normally open contact (EF008256)
Feature value0
Feature nameNumber of contacts as change-over contact (EF008257)
Feature value2
Feature nameWidth (EF000008)
Feature value45 mm
Feature nameHeight (EF000040)
Feature value90 mm
Feature nameDepth (EF000049)
Feature value113 mm

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.