Product successfully added to your shopping cart
EMD-FL-3V-400
2866064
PHOENIX_CONTACT
1
Monitoring relay
Supervisory relay for 3-phase voltage monitoring of 280...520 V AC, undervoltage, Window, phase sequence, phase fault, asymmetry, long-range power supply, 2 switched contacts
Relays > Voltage monitoring relay
Industrial Relays
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Orderkey | 2866064 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 268 (C-5-2017) |
| GTIN | 4017918975029 |
| Weight per Piece (excluding packing) | 164.000 g |
| Custom tariff number | 85364900 |
| Country of origin | AT (Austria) |
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| -25 °C ... 40 °C (corresponds to UL 508) | |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Nominal input voltage UN | 3 N ~ 400/230 V |
|---|---|
| Maximum temperature coefficient | < 0.1 %/K |
| Function | Undervoltage, window, asymmetry, phase sequence, phase failure |
| Min. setting range | -30 % ... 20 % (From UN) |
| Max. setting range | -20 % ... 30 % (From UN) |
| Min setting range of the voltage threshold value | 280 V AC ... 480 V AC |
| Max. setting range of the voltage threshold value | 320 V AC ... 520 V AC |
| Setting range for response delay | 0.1 s ... 10 s |
| Basic accuracy | ± 5 % (of scale end value) |
| Setting accuracy | ≤ 5 % (of scale end value) |
| Repeat accuracy | ≤ 2 % |
| Asymmetry | 5 % ... 25% / OFF |
| Recovery time | 500 ms |
| Contact type | 2 floating PDT contacts |
|---|---|
| Maximum switching voltage | 250 V AC (in acc. with IEC 60664-1) |
| Interrupting rating (ohmic load) max. | 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing) |
| 1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing) | |
| Output fuse | 5 A (fast-blow) |
| Supply voltage | 230 V AC |
|---|---|
| 24 V DC | |
| Supply voltage range | 24 V AC ... 240 V AC -15 % ... +10 % |
| 24 V DC ... 240 V DC -20 % ... +25 % |
| Mechanical service life | approx. 2x 107cycles |
|---|---|
| Operating mode | 100% operating factor |
| Mounting position | any |
| Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
| Electromagnetic compatibility | Conformance with EMC directive |
| Overvoltage category | III, basic insulation (as per EN 50178) |
| Housing insulation material | Polyamide PA, self-extinguishing |
| Color | green |
| Rated insulation voltage | 300 V (acc. to EN 50178) |
| Conformance | CE-compliant |
| UL, USA/Canada | UL/C-UL listed UL 508 |
| Conductor cross section flexible min. | 0.25 mm² |
|---|---|
| Conductor cross section flexible max. | 2.5 mm² |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.5 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.25 mm² ... 2.5 mm² |
| Conductor cross section AWG | 20 ... 14 |
| Tightening torque | 1 Nm |
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 |
| Low Voltage Directive | Conformance with Low Voltage Directive |
| Conformance | CE-compliant |
| UL, USA/Canada | UL/C-UL listed UL 508 |
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |
| Feature Name | Feature Value |
|---|---|
| Type of electric connection (EF003961) | Screw connection |
| With detachable clamps (EF003340) | No |
| Voltage measuring range 1 (EF006134) | 280 V |
| Type of voltage measuring range (EF003399) | AC |
| Single-phase under voltage possible (EF003390) | No |
| Three-phase under voltage possible (EF003391) | Yes |
| Single-phase over voltage possible (EF003392) | No |
| Three-phase over voltage possible (EF003393) | No |
| Single-phase hysteresis possible (EF003394) | No |
| Three-phase hysteresis possible (EF003395) | Yes |
| Contains function DC-under voltage (EF003396) | No |
| Contains function DC-over voltage (EF003397) | No |
| Contains function DC-voltage hysteresis (EF003398) | No |
| Number of contacts as normally closed contact (EF008255) | 0 |
| Number of contacts as normally open contact (EF008256) | 0 |
| Number of contacts as change-over contact (EF008257) | 2 |
| Width (EF000008) | 22.5 mm |
| Height (EF000040) | 90 mm |
| Depth (EF000049) | 113 mm |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOG PHOENIX INTERFACE TECHNOLOGY AND SWITCHING DEVICES EN .pdf | 28 Mbytes |
|
| PHOENIX CONTACT-2866064-EMD-FL-3V-400 | 118 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.