Modular terminal block with three-stage surge protection for two signal wires with common reference potential, separate ground connection, nominal voltage: 24 V DC, for mounting on NS 35/7.5, terminal width: 6.2 mm, terminal height: 54.6 mm

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection for measurement and control technology - PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
10+$71.20
20+$70.76
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Height79.6 mm
Width6.2 mm
Depth54.6 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorblack
Standards for cearances and creepage distancesIEC 60664-1
Mounting typeDIN rail: 35 mm
TypeDouble-level terminal block with PE foot – separate PE connection
Number of positions2
Direction of actionLine-Earth Ground

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC30 V DC
Maximum continuous voltage UC (wire-ground)30 V DC
Nominal current IN300 mA (40°C)
Operating effective current IC at UC≤ 10 µA (per path)
Standby power consumption PC≤ 1430 mVA
Residual current IPE≤ 10 µA (per path)
Nominal discharge current In (8/20) µs (Core-Earth)5 kA
Total surge current (8/20) µs10 kA
Nominal pulse current Ian (10/1000) µs (Core-Earth)100 A
Impulse discharge current (10/350)˽µs, peak value limp500 A
Output voltage limitation at 1 kV/µs (Core-Earth) spike≤ 50 V
Voltage protection level Up (core-ground)≤ 90 V (C2 - 10 kV / 5 kA)
≤ 55 V (C1 - 1 kV/500 A)
≤ 45 V (C3 - 10 A)
≤ 50 V (C3 - 100 A)
≤ 130 V (D1 - 500 A)
Response time tA (Core-Earth)≤ 1 ns
Input attenuation aE, asym.0.4 dB (≤ 200 kHz / 50 Ω)
0.1 dB (≤ 30 kHz/150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 50 Ohm systemtyp. 1.5 MHz
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm systemtyp. 550 kHz
Capacity (Core-Core)≤ 4 nF
Resistance in series6.6 Ω ±20 %
6.6 Ω
Surge protection fault messageNone
Max. required back-up fuse315 mA (T/IEC 60127-2/3)
Impulse durability (conductor-ground)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 100 A
D1 (500 A)
Alternating current carrying capacity (conductor-ground)0.5 A/1 s

Connection data

Connection methodScrew connection
Connection type INScrew terminal blocks
Connection type OUTScrew terminal blocks
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14

Datasheet - PDF

Title: Language: Size: Type:
PHOENIX CONTACT-2838173-TT-2/2- 24DC English 143 Kbytes PHOENIX CONTACT-2838173-TT-2/2- 24DC

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Últimas Opiniones de Nuestros Clientes

Todas las valoraciones que recibimos de los artículos que ofrecemos son reales y están verificadas. Un pequeño gesto, pero de mucho valor. Por eso, te agradecemos ese minuto que inviertes en dejarnos tu opinión y calificación sobre los productos, porque nos ayuda a seguir mejorando y a ofrecerte un servicio de todavía mayor calidad.