MCR-FL-TS-LP-I-EX 2864587 PHOENIX CONTACT MCR temperature measuring transducers, resistance thermometers, th.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MCR-FL-TS-LP-I-EX 2864587 PHOENIX CONTACT MCR temperature measuring transducers, resistance thermometers, th..

MCR-FL-TS-LP-I-EX

2864587

PHOENIX_CONTACT

Available

Ship on today

MCR temperature measuring transducers, resistance thermometers, thermocouples, resistance and voltage sensors

More details


Programmable Logic Controllers Plcs

INTERFACE Signal converters, switching devices, and power supply units - PHOENIX CONTACT

MSR Components for Ex areas - PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
1+$435.47
2+$420.50
3+$413.48
4+$410.99
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Width12.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Degree of protectionIP20

Input data

Configurable/programmableYes, programmable
Sensor types (RTD) that can be usedPt, Ni (100, 500, 1000); min. measurement range 10 K
Sensor types that can be used (TC)B, C, D, E, J, K, L, N, R, S, T, U; min. measurement range 50 K/500 K
Connection method2, 3, 4-wire
Input signal range10 Ω ... 400 Ω (min. measurement range 10 Ω)
10 Ω ... 2000 Ω (min. measurement range 100 Ω)
-10 mV ... 100 mV (min. measurement range 5 mV)

Output data

Signal outputCurrent output
Current output signal4 mA ... 20 mA
20 mA ... 4 mA
Max. current output signal≤ 23 mA
Output current with short-circuit≤ 3.6 mA or ≥ 21 mA (adjustable, not for thermocouples)
Output current with wire break≤ 3.6 mA or ≥ 21 mA (adjustable)
Output current range with overrange/underrange3.8 mA ... 20.5 mA
Load/output load current output≤ 520 Ω (At UV = 24 V; Usupply - 12 V / 0.023 A)

Power supply

DesignationLoop-powered
Supply voltage range12 V DC ... 30 V DC
Max. current consumption< 3.5 mA

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length8 mm
Screw threadM3
Connection methodScrew connection
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

General

Step response (10-90%)< 2 s
Switch-on delay4 s
ConfigurationWith HART protocol
Flammability rating according to UL 94V0
Standards/regulationsNAMUR recommendation NE 21
Housing materialPolyamide PA non-reinforced
Colorgreen
Line monitoringNE 43
ConformanceCE-compliant
ATEXEx II 2(1) G Ex ia IIC T6
UL, USA / CanadacULus
Functional Safety (SIL)SIL 2

Safety data

Max. output voltage Uo5 V DC
Max. output current Io5.9 mA
Max. output power Po7.2 mW
Max. ambient temperatureT4 = 85 °C, T5 = 70 °C, T6 = 55 °C
GroupIIA
Max. external inductivity Lo100 mH
Max. external capacity Co10 µF
GroupIIB
Max. external inductivity Lo100 mH
Max. external capacity Co10 µF
GroupIIC
Max. external inductivity Lo100 mH
Max. external capacity Co2 µF
Safety-related maximum voltage Um250 V

Datasheet - PDF

Title: Language: Size: Type:
PHOENIX CONTACT-2864587-MCR-FL-TS-LP-I-EX English 128 Kbytes PHOENIX CONTACT-2864587-MCR-FL-TS-LP-I-EX

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.