ANUNCIAR
MACX MCR-SL-NAM-2RO 2865010 PHOENIX CONTACT Isolation amplifier View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MACX MCR-SL-NAM-2RO 2865010 PHOENIX CONTACT Isolation amplifier

MACX MCR-SL-NAM-2RO

2865010

PHOENIX_CONTACT

Isolation amplifier

NAMUR separation amplifier for the operation of proximity detectors and switches. The signals are transmitted to the control level via 2 separate relay outputs (normally open contact). Cable Fault Detection (LFD), Galvanic 3-Way Spacing, SIL 2, Screw Connection.

More details


Sensors > NAMUR switching amplifier

INTERFACE Components (IF)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total: $275.58
Unit price: $275.58
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Key Commercial Data

Orderkey2865010
Packing unit1 pc
Catalog pagePage 133 (C-5-2017)
GTIN4046356491686
Weight per Piece (excluding packing)140.000 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restriction1

Dimensions

Width12.5 mm
Height112.5 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 2000 m
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Noise immunityEN 61000-6-2 EN 61326

Input data

Non-load voltage~ 8 V DC
Switching points (attenuated)< 1.2 mA (blocking)
Switching points (unattenuated)> 2.1 mA (conductive)
Available input sourcesNAMUR proximity sensors (EN 60947-5-6)
Short-circuit current~ 8 mA
Switching hysteresis< 0.2 mA
Line fault detectionBreak 0.05 mA < IIN < 0.35 mA
Short circuit 100 Ω < RSensor < 360 Ω

Output data

Switching outputRelay output
Contact type2 N/O contacts
Contact materialAgSnO2, hard gold-plated
Maximum switching voltage250 V AC (2 A)
120 V DC (0.2 A)
30 V DC (2 A)
Maximum switching capacity500 VA
Mechanical service life107cycles
Switching frequency≤ 20 Hz (without load)

Power supply

Nominal supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
Max. current consumption30 mA (24 V DC)
Power dissipation< 950 mW
Power consumption< 950 mW

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length7 mm
Screw threadM3
Connection methodScrew connection
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

General

No. of channels1
Status displayGreen LED (supply voltage)
LED yellow (switching state)
Red LED (line errors)
Flammability rating according to UL 94V0
Degree of pollution2
Overvoltage categoryIII
Electromagnetic compatibilityConformance with EMC directive
Interference emissionEN 61000-6-4
Housing materialPA 6.6-FR
Colorgray
DesignationInput/supply, DIN rail connector
Electrical isolation300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1))
DesignationOutput 1/output 2/input, power supply, DIN rail connector
Electrical isolation300 Vrms(Rated insulation voltage (overvoltage category III; degree of pollution 2, safe isolation as per EN 61010-1))
DesignationOutput 1/output 2/input/power supply, DIN rail connector
Electrical isolation2.5 kV (50 Hz, 1 min., test voltage)
ConformanceCE-compliant, additionally EN 61326-1
ATEX II 3 G Ex nA nC IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
SIL2

Safety characteristic data

Integrity requirementIEC 61508 - Low demand
DesignationNon-inverted operation
Equipment typeType A
Safety Integrity Level (SIL)2
Safe Failure Fraction (SFF)78 %
λSU2.49 x 10-7(249 FIT)
λSD6 x 10-9(6 FIT)
λDU6.4 x 10-8(64 FIT)
λDD7 x 10-9(7 FIT)
Probability of a hazardous failure on demand (PFDAVG)3.09 x 10-4(1 year)
6.17 x 10-4(2 years)
1.54 x 10-3(5 years)
Diagnostic coverage (DC)DCS= 2.4 %, DCD= 9 %
Integrity requirementIEC 61508 - Low demand
DesignationInverted operation
Equipment typeType A
Safety Integrity Level (SIL)2
Safe Failure Fraction (SFF)78 %
λSU2.48 x 10-7(248 FIT)
λSD1 x 10-9(1 FIT)
λDU6.2 x 10-8(62 FIT)
λDD6 x 10-9(6 FIT)
Probability of a hazardous failure on demand (PFDAVG)3.01 x 10-4(1 year)
6.02 x 10-4(2 years)
1.5 x 10-3(5 years)
Diagnostic coverage (DC)DCS= 0.4 %, DCD= 8 %
Safety Integrity Level (SIL)1

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Flammability rating according to UL 94V0
ConformanceCE-compliant, additionally EN 61326-1
ATEX II 3 G Ex nA nC IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
DNV GL-TemperatureB
DNV GL-HumidityB
DNV GL-VibrationA
DNV GL-EMCB
DNV GL-EnclosureRequired protection according to the Rules shall be provided upon installation on board

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2865010 Sensors (EC001485)
Feature Name Feature Value
Type of power supply (EF001469) Other
Rated supply voltage DC (EF007078) 19.2 V
Number of inputs according to NAMUR (EF006886) 1
Number of inputs, potential-free (EF006887) 1
Switching voltage (EF003586) 250 V
Switching power (EF001313) 500 VA
Number of channels (EF000259) 1
Number of output circuits relays normally open contact (EF006992) 2
Number of output circuits relays change-over contact (EF006993) 0
Number of output circuits transistor potential-free (EF006997) 0
Number of output circuits transistor pnp (EF006996) 0
Number of output circuits transistor npn (EF006995) 0
Number of output circuits transistor antivalent (EF006994) 0
Number of output circuits opto-coupler (EF006991) 0
Malfunction message output (EF007499) No
Inherently safe according to EN 60947-5-6 NAMUR (EF007112) No
Galvanic separation between inputs (EF007224) No
Galvanic separation between input and output (EF007223) Yes
Galvanic separation between output to output (EF007222) Yes
Galvanic separation between supply voltage and all other current circuits (EF007225) Yes
Suitable for safety functions (EF001597) Yes
Performance level according to EN ISO 13849-1 (EF007399) None
Width (EF000008) 12.5 mm
Height (EF000040) 112.5 mm
Power consumption (EF000346) 0.95 W
Operating temperature (EF002393) -40 °C
Construction type of device (EF007276) Built-in device
Type of electric connection (EF003961) Screw connection
Mounting method (EF000003) Other
Depth (EF000049) 113.7 mm
Degree of protection (IP) (EF005474) IP20

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.