ILB ETH 24 DI16 DIO16-2TX 2832962 PHOENIX CONTACT I/O module View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

ILB ETH 24 DI16 DIO16-2TX 2832962 PHOENIX CONTACT I/O module

ILB ETH 24 DI16 DIO16-2TX

2832962

PHOENIX_CONTACT

I/O module

Inline, Block IO, Ethernet, RJ45 Female, Digital inputs: 32, 24 V DC, connection technology: 3 conductors, Digital outputs: 16, 24 V DC, 500 mA, connection technology: 2 conductors, protection index: IP20, including Inline connectors and fields

More details


I/O

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Key Commercial Data

Orderkey2832962
Packing unit1 pc
Catalog pagePage 188 (C-6-2017)
GTIN4046356012324
Weight per Piece (excluding packing)500.000 g
Custom tariff number85389091
Country of originDE (Germany)

Note

Utilization restriction1

Dimensions

Dimensional drawing
Width156 mm
Height141 mm
Depth57 mm
Note on dimensionsSpecfications with connectors

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)max. 85 % (non-condensing)
Air pressure (operation)80 kPa ... 108 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)66 kPa ... 108 kPa (up to 3500 m above sea level)
Degree of protectionIP20

General

Mounting typeDIN rail
Net weight500 g
Note on weight specificationswith connectors
Diagnostics messagesShort-circuit / overload of the digital outputs Message in the diagnostics register
Short-circuit, sensor supply Message in the diagnostics register
Undervoltage Power supply for sensors Message in the diagnostics register
Mounting typeNS 35/7,5

Interfaces

DesignationEthernet
No. of channels2
Connection methodRJ45 socket
Transmission speed10/100 Mbps (with auto negotiation)
Transmission physicsCopper

Digital inputs

Input nameDigital inputs
Description of the input16 fixed and 16 freely selectable
Connection methodSpring-cage connection
Connection technology3-wire
Number of inputs32
Typical response timeapprox. 500 µs
Type of protectionShort-circuit protection, overload protection of the sensor supply
Nominal input current at UINtyp. 5 mA
Delay at signal change from 0 to 1500 µs

Digital outputs

Output nameDigital outputs
Connection methodSpring-cage connection
Connection technology2-wire
Number of outputs16
Type of protectionShort-circuit and overload protection
Nominal output voltage24 V DC
Maximum output current per channel500 mA

Electrical isolation

Test sectionI/O / Logic 500 V AC 50 Hz 1 min.
I/O area / FE 500 V AC 50 Hz 1 min.
Logic / FE 500 V AC 50 Hz 1 min.

Standards and Regulations

Noise emissionIndustrial environment
Mechanical testsVibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 25g
Connection in acc. with standardCUL

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.