UKH 240-3L/N 3076390 PHOENIX CONTACT High-current terminal block View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

UKH 240-3L/N 3076390 PHOENIX CONTACT High-current terminal block

UKH 240-3L/N

3076390

PHOENIX_CONTACT

2

High-current terminal block

More details


Modular TBs

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey3076390
Packing unit2 pc
Minimum order quantity2 pc
NoteMade to Order (non-returnable)
Catalog pagePage 267 (C-1-2017)
GTIN4046356653978
Weight per Piece (excluding packing)1,986.000 g
Custom tariff number85369010
Country of originPL (Poland)

General

Number of positions4
Number of levels1
Number of connections8
Potentials4
Nominal cross section240 mm²
Colorgray/blue
Insulating materialPA
Flammability rating according to UL 94V0
Rated surge voltage8 kV
Degree of pollution3
Overvoltage categoryIII
Insulating material groupI
Maximum power dissipation for nominal condition13.78 W
Maximum load current415 A (with 240 mm² conductor cross section)
Nominal current IN415 A
Nominal voltage UN1000 V
Open side panelNo
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))130 °C
Static insulating material application in cold-60 °C
Behavior in fire for rail vehicles (DIN 5510-2)Test passed
Flame test method (DIN EN 60695-11-10)V0
Oxygen index (DIN EN ISO 4589-2)>32 %
NF F16-101, NF F10-102 Class I2
NF F16-101, NF F10-102 Class F2
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Calorimetric heat release NFPA 130 (ASTM E 1354)28 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Dimensions

Width144 mm
Length100 mm
Height123.6 mm
Height NS 35/15131.5 mm
Height NS 32129 mm

Connection data

NoteScrews with hexagonal socket
Connection methodScrew connection
Screw threadM10
Stripping length40 mm
Tightening torque, min25 Nm
Tightening torque max30 Nm
Connection in acc. with standardIEC 60947-7-1
NoteNote: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area.
Conductor cross section solid min.70 mm²
Conductor cross section solid max.240 mm²
Conductor cross section AWG min.2/0
Conductor cross section AWG max.500 kcmil
Conductor cross section flexible min.70 mm²
Conductor cross section flexible max.240 mm²
Min. AWG conductor cross section, flexible2/0
Max. AWG conductor cross section, flexible500 kcmil
Conductor cross section flexible, with ferrule without plastic sleeve min.70 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.185 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.70 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.185 mm²
Cross section with insertion bridge, solid max.240 mm²
Cross section with insertion bridge, stranded max.185 mm²
2 conductors with same cross section, solid min.35 mm²
2 conductors with same cross section, solid max.95 mm²
2 conductors with same cross section, stranded min.50 mm²
2 conductors with same cross section, stranded max.95 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min.35 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max.50 mm²
Internal cylindrical gageB15

Standards and Regulations

Connection in acc. with standardUL
IEC 60947-7-1
Flammability rating according to UL 94V0
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.