STU 2,5-TWIN 3033016 PHOENIX CONTACT Feed-through terminal block View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

STU 2,5-TWIN 3033016 PHOENIX CONTACT Feed-through terminal block

STU 2,5-TWIN

3033016

PHOENIX_CONTACT

50

Feed-through terminal block

Feed-through terminal, nominal voltage: 800 V, nominal current: 24 A, connection type: Spring connection, Sizing cross-section: 2.5 mm², cross-section: 0.08 mm² - 4 mm², connection type: Screw connection, Sizing cross-section: 2.5 mm², cross-section: 0.14 mm² - 4 mm², mounting: NS 35/7.5, NS 35/15, color: gray

Feed-through terminal block, nom. voltage: 800 V, nominal current: 24 A, connection method: Spring-cage connection, Rated cross section: 2.5 mm2, cross section: 0.08 mm2 - 4 mm2, connection method: Screw connection, Rated cross section: 2.5 mm2, cross section: 0.14 mm2 - 4 mm2, mounting: NS 35/7,5, NS 35/15, color: gray

More details


Modular TBs

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Technical data

Product properties
Product typeHybrid terminal block
Number of connections3
Number of rows1
Potentials1
Data management status
Article revision07
Insulation characteristics
Overvoltage categoryIII
Degree of pollution3

Electrical properties
Rated surge voltage8 kV
Maximum power dissipation for nominal condition0.77 W

Connection data
Number of connections per level3
Nominal cross section2.5 mm²
Level 1 above 1+2
Stripping length8 mm ... 10 mm
Connection in acc. with standardIEC 60947-7-1
Conductor cross section rigid0.08 mm² ... 4 mm²
Cross section AWG28 ... 12 (converted acc. to IEC)
Conductor cross section flexible0.08 mm² ... 2.5 mm²
Conductor cross section, flexible [AWG]28 ... 14 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)0.14 mm² ... 2.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.14 mm² ... 2.5 mm²
Nominal current24 A
Maximum load current28 A (The maximum load current must not be exceeded by the total current of all connected conductors.)
Nominal voltage800 V
Nominal cross section2.5 mm²
Level 1 below 1
Screw threadM3
Tightening torque0.6 ... 0.8 Nm
Connection in acc. with standardIEC 60947-7-1
Conductor cross section rigid0.14 mm² ... 4 mm²
Cross section AWG26 ... 12 (converted acc. to IEC)
Conductor cross section flexible0.14 mm² ... 2.5 mm²
Conductor cross section, flexible [AWG]26 ... 14 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)0.25 mm² ... 2.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.5 mm² ... 1.5 mm²
Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve)0.5 mm² ... 1.5 mm²
2 conductors with same cross section, solid0.14 mm² ... 1.5 mm²
2 conductors with same cross section, flexible0.14 mm² ... 1.5 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve0.25 mm² ... 1.5 mm²
Nominal current24 A
Maximum load current28 A (with 4 mm² conductor cross section)
Nominal voltage800 V
Nominal cross section2.5 mm²

Dimensions
Width5.2 mm
End cover width2.2 mm
Height65.3 mm
Depth on NS 35/7,542.8 mm
Depth on NS 35/1550.3 mm

Material specifications
Colorgray (RAL 7042)
Flammability rating according to UL 94V0
Insulating material groupI
Insulating materialPA
Static insulating material application in cold-60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))130 °C
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354)28 MJ/kg
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed

Electrical tests
Surge voltage test
Test voltage setpoint9.8 kV
ResultTest passed
Temperature-rise test
Requirement temperature-rise testIncrease in temperature ≤ 45 K
ResultTest passed
Short-time withstand current 2.5 mm²0.3 kA
Short-time withstand current 4 mm²0.48 kA
ResultTest passed
Power-frequency withstand voltage
Test voltage setpoint2 kV
ResultTest passed

Mechanical properties
Mechanical data
Open side panelYes

Mechanical tests
Mechanical strength
ResultTest passed
Attachment on the carrier
DIN rail/fixing supportNS 35
Test force setpoint1 N
ResultTest passed
Test for conductor damage and slackening
Rotation speed10 rpm
Revolutions135
Conductor cross section/weight0.08 mm² / 0.1 kg
2.5 mm² / 0.7 kg
4 mm² / 0.9 kg
ResultTest passed

Environmental and real-life conditions
Aging
Temperature cycles192
ResultTest passed
Needle-flame test
Time of exposure30 s
ResultTest passed
Oscillation/broadband noise
SpecificationDIN EN 50155 (VDE 0115-200):2008-03
SpectrumService life test category 2, bogie-mounted
Frequencyf1= 5 Hz to f2= 250 Hz
ASD level6.12 (m/s²)²/Hz
Acceleration3.12g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
ResultTest passed
Shocks
SpecificationDIN EN 50155 (VDE 0115-200):2008-03
Pulse shapeHalf-sine
Acceleration30g
Shock duration18 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
ResultTest passed
Ambient conditions
Ambient temperature (operation)-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
Ambient temperature (storage/transport)-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)-5 °C ... 70 °C
Ambient temperature (actuation)-5 °C ... 70 °C
Permissible humidity (storage/transport)30 % ... 70 %

Standards and regulations
Connection in acc. with standardIEC 60947-7-1
IEC 60947-7-1

Mounting
Mounting typeNS 35/7,5
NS 35/15

ETIM for 3033016 Terminal blocks (EC000897)
Feature Name Feature Value
Rated current In (EF008250) 24 A
Rated voltage (EF000228) 800 V
Type of electrical connection 1 (EF002526) Spring clamp connection
Type of electrical connection 2 (EF002527) Screw connection
Number of levels (EF002659) 1
Number of clamp positions per level (EF002660) 3
Suitable for conductor material (EF012572) Aluminium/copper
Mounting method (EF000003) DIN rail (top hat rail) 35 mm
Material insulation body (EF007543) Other
Inflammability class of insulation material according to UL94 (EF002521) V0
Width (EF000008) 5.2 mm
Height (EF000040) 65.3 mm
Depth (EF000049) 42.8 mm
Closing plate required (EF002525) Yes
Colour (EF000007) Grey
Internally connected stages (EF002661) Yes

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.