Power/input isolating amplifier
Intrinsically safe input and power signal conditioner with HART transparency. Transmits 0/4 signals ... 20 mA powered or active from the Ex zone to a load (active or passive) in the safe zone. SIL 2 (1oo1) / SIL 3 (1oo2), wide range power.
Ex i repeater power supply and input signal conditioner, HART-transparent. Transmits supplied or active 0/4 … 20 mA signals from the Ex area to a load (active or passive) in the safe area. SIL 2 (1oo1) / SIL 3 (1oo2), wide-range supply.
Sensors > Isolation amplifier
INTERFACE Components (IF)
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Product type | Repeater power supply |
| Product family | MACX Analog |
| Application | Analog IN |
| No. of channels | 1 |
| Type | Ex i signal conditioners with SIL functional safety |
| Configuration | DIP switches |
| Data management status | |
| Article revision | 14 |
| Electrical isolation | 3-way isolation |
| Electrical isolation between input and output | yes |
| Step response (10-90%) | < 600 µs (for 4 mA ... 20 mA step) |
| Maximum temperature coefficient | < 0.01 %/K |
| Maximum transmission error | < 0.1 % (of final value) |
| Transmission error, typical | < 0.05 % (of final value) |
| Electrical isolation | |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) |
| Overvoltage category | II |
| Pollution degree | 2 |
| Electrical isolation Input/output/power supply IEC/EN 61010-1 | |
| Standards/regulations | IEC/EN 61010-1 |
| Rated insulation voltage | 300 Vrms |
| Insulation | Safe isolation |
| Electrical isolation Input/output IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 |
| Rated insulation voltage | 265 Vrms |
| Electrical isolation Input/power supply IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 |
| Rated insulation voltage | 265 Vrms |
| Electrical isolation Output/supply IEC/EN 60079-7 | |
| Standards/regulations | IEC/EN 60079-7 |
| Rated insulation voltage | 265 Vrms |
| Supply | |
| Designation | Repeater power supply operation |
| Nominal supply voltage range | 24 V AC/DC ... 230 V AC/DC -20 % ... +10 % (50/60 Hz) |
| Supply voltage range | 19.2 V AC/DC ... 253 V AC/DC (50/60 Hz) |
| Max. current consumption | < 80 mA (24 V DC / 20 mA) |
| Power dissipation | < 1.6 W (24 V DC / 20 mA) |
| Power consumption | < 2.2 W |
| Supply | |
| Designation | Signal conditioner operation |
| Nominal supply voltage range | 24 V AC/DC ... 230 V AC/DC -20 % ... +10 % (50/60 Hz) |
| Supply voltage range | 19.2 V AC/DC ... 253 V AC/DC (50/60 Hz) |
| Max. current consumption | < 45 mA (24 V DC / 20 mA) |
| Power dissipation | < 1.1 W (24 V DC / 20 mA) |
| Signal: Repeater power supply operation | |
| Description of the input | Active current input, intrinsically safe |
| Number of inputs | 1 |
| Current input signal | 4 mA ... 20 mA |
| Transmitter supply voltage | > 16 V (20 mA) |
| > 15.3 V (22.5 mA) | |
| Signal: Signal conditioner operation | |
| Description of the input | Passive current input, intrinsically safe |
| Current input signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| Voltage drop | < 3.5 V (in input isolating amplifier operation) |
| Signal: Repeater power supply operation | |
| Output description | Current output (active and passive) |
| Number of outputs | 1 |
| Voltage output signal | 1 V ... 5 V (internal resistance, 250 Ω, 0.1%) |
| Configurable via DIP switches | |
| Current output signal | 4 mA ... 20 mA (active) |
| 4 mA ... 20 mA (14 ... 26 V ext. source voltage) | |
| Load/output load current output | < 600 Ω (20 mA) |
| < 525 Ω (22.5 mA) | |
| Output ripple | < 20 mVrms |
| Output behavior in the event of an error | 0 mA (Cable break in the input) |
| ≥ 22.5 mA (Cable short-circuit in the input) | |
| Signal: Signal conditioner operation | |
| Output description | Current output (active and passive) |
| Voltage output signal | 0 V ... 5 V (internal resistance, 250 Ω, 0.1%) |
| 1 V ... 5 V (internal resistance, 250 Ω, 0.1%) | |
| Current output signal | 0 mA ... 20 mA (active) |
| 4 mA ... 20 mA (active) | |
| 0 mA ... 20 mA (14 ... 26 V ext. source voltage) | |
| 4 mA ... 20 mA (14 ... 26 V ext. source voltage) | |
| Load/output load current output | < 600 Ω (20 mA) |
| < 525 Ω (22.5 mA) | |
| Output ripple | < 20 mVrms |
| Output behavior in the event of an error | 0 mA (Cable break in the input) |
| 0 mA (Cable short-circuit in the input) | |
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible (2 conductors with same cross section) | 0.25 mm² ... 0.34 mm² (TWIN ferrule without plastic sleeve) |
| 0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve) | |
| Conductor cross section AWG | 24 ... 14 |
| 24 ... 22 (TWIN ferrule without plastic sleeve) | |
| 20 ... 16 (TWIN ferrule with plastic sleeve) |
| Ex installation (EPL) | Gc |
| Div. 2 | |
| Ex i circuits (EPL) | Ga |
| Da | |
| Ma | |
| Div. 1 | |
| Safety data: Repeater power supply operation | |
| Max. output voltage Uo | 25.2 V |
| Max. output current Io | 93 mA |
| Max. output power Po | 587 mW |
| Safety-related maximum voltage Um | 253 V AC/DC (Supply terminals) |
| 253 V AC (Output terminals) | |
| 125 V DC (Output terminals) | |
| I (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 40 mH / 4.8 µF |
| IIA (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 26 mH / 2.9 µF |
| IIB (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 14 mH / 820 nF |
| IIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 3 mH / 107 nF |
| IIA (mixed circuit): Max. external inductivity Lo/ Max. external capacitance Co | 26 mH / 470 nF, 20 mH / 570 nF, 1 mH / 630 nF, 0.5 mH / 720 nF, 0.1 mH / 1.1 µF, 0.005 mH / 2.9 µF |
| IIB/III (mixed circuit): Max. external inductivity Lo/ Max. external capacitance Co | 16 mH / 370 nF, 500 µH / 510 nF, 200 µH / 660 nF, 100 µH / 820 nF |
| IIC (mixed circuit): Max. external inductivity Lo/ Max. external capacitance Co | 2.2 mH / 47 nF, 2 mH / 49 nF, 1 mH / 63 nF, 500 µH / 80 nF, 200 µH / 107 nF |
| I (mixed circuit): Max. external inductivity Lo/ Max. external capacitance Co | 37 mH / 0.54 µF, 0.35 mH / 1 µF, 0.009 mH / 2.9 µF, 0.001 mH / 4.15 µF |
| Safety data: Signal conditioner operation | |
| Input voltage Ui | ≤ 30 V |
| Input current Ii | ≤ 150 mA |
| Max. internal inductance Li | negligible |
| Max. internal capacitance Ci | negligible |
| Safety-related maximum voltage Um | 253 V AC/DC (Supply terminals) |
| 253 V AC (Output terminals) | |
| 125 V DC (Output terminals) | |
| Data communication (bypass) | |
| HART function | Yes |
| Protocols supported | HART-transparent |
| Status display | Green LED (supply voltage) |
| Dimensional drawing | ![]() |
| Width | 17.5 mm |
| Height | 107.9 mm |
| Depth | 113.7 mm |
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V0 (Housing) |
| Housing material | PA 6.6-FR |
| Ambient conditions | |
| Degree of protection | IP20 (not assessed by UL) |
| Ambient temperature (operation) | -40 °C ... 60 °C (Any mounting position) |
| -40 °C ... 70 °C (Derating) | |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Altitude range (≤ 2000 m) | |
| Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
| Ambient temperature (operation) | -40 °C ... 60 °C |
| -40 °C ... 70 °C (Derating) | |
| Rated insulation voltage | 375 VPP(Power supply, input / output) |
| Altitude range (≤ 3000 m) | |
| Height range | > 2000 m ... 3000 m |
| Ambient temperature (operation) | -40 °C ... 54 °C |
| -40 °C ... 63 °C (Derating) | |
| Rated insulation voltage | 190 V AC (Power supply, input / output) |
| 110 V DC (Power supply, input / output) | |
| Altitude range (≤ 4000 m) | |
| Height range | > 3000 m ... 4000 m |
| Ambient temperature (operation) | -40 °C ... 48 °C |
| -40 °C ... 56 °C (Derating) | |
| Rated insulation voltage | 60 V AC/DC (Power supply, input / output) |
| Altitude range (≤ 5000 m) | |
| Height range | > 4000 m ... 5000 m |
| Ambient temperature (operation) | -40 °C ... 42 °C |
| -40 °C ... 49 °C (Derating) | |
| Rated insulation voltage | 60 V AC/DC (Power supply, input / output) |
| CE | |
| Certificate | CE-compliant |
| Note | and EN 61326 |
| ATEX | |
| Identification | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3(1) G Ex ec [ia Ga] IIC T4 Gc | |
| I (M1) [Ex ia Ma] I | |
| Certificate | BVS 08 ATEX E 094 X |
| IECEx | |
| Identification | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex ec [ia Ga] IIC T4 Gc | |
| [Ex ia Ma] I | |
| Certificate | IECEx BVS 08.0035X |
| CCC / China-Ex | |
| Identification | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex ec [ia Ga] IIC T4 Gc | |
| Certificate | 2022122316115974 |
| UL, USA/Canada | |
| Identification | Class I Div 2; IS for Class I, II, III Div 1 |
| Certificate | , C.D.-No 83104549 |
| Safety Integrity Level (SIL / SILCL, IEC 61508) | |
| Identification | 2 |
| Certificate | ZP/C031/20 |
| Systematic Capability (SC / SILCL) | |
| Identification | 3 |
| INMETRO | |
| Identification | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex ec [ia Ga] IIC T4 Gc | |
| Certificate | DNV 18.0138 X |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise immunity | EN 61000-6-2 |
| Note | When being exposed to interference, there may be minimal deviations. |
| Noise emission | EN 61000-6-4 |
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| Typical deviation from the measuring range final value | 1 % |
| Fast transients (burst) | |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Typical deviation from the measuring range final value | 1 % |
| Conducted interference | |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Typical deviation from the measuring range final value | 1 % |
| Electrical isolation | 3-way isolation |
| GB Standard | |
| Standards/regulations | GB/T 3836.1 |
| GB/T 3836.3 | |
| GB/T 3836.4 | |
| GB/T 16935.1 | |
| Mounting type | DIN rail mounting |
| Feature Name | Feature Value |
|---|---|
| Type of power supply (EF001469) | Other |
| Rated supply voltage AC (EF007075) | 19.2 V |
| Rated supply voltage DC (EF007078) | 19.2 V |
| Number of input ranges -60 mV ... +60 mV (EF006927) | 0 |
| Number of input ranges -100 mV ... +100 mV (EF006912) | 0 |
| Number of input ranges -300 mV ... +300 mV (EF006920) | 0 |
| Number of input ranges -500 mV ... +500 mV (EF006926) | 0 |
| Number of input ranges -1 V ... +1 V (EF006906) | 0 |
| Number of input ranges -2 V ... +2 V (EF006913) | 0 |
| Number of input ranges -2.5 V ... +2.5 V (EF006915) | 0 |
| Number of input ranges -5 V ... +5 V (EF006923) | 0 |
| Number of input ranges -10 V ... +10 V (EF006909) | 0 |
| Number of input ranges -20 V ... +20 V (EF006917) | 0 |
| Number of input ranges 0 mV ... 60 mV (EF006905) | 0 |
| Number of input ranges 0 mV ... 100 mV (EF006893) | 0 |
| Number of input ranges 0 mV ... 200 mV (EF006898) | 0 |
| Number of input ranges 0 mV ... 300 mV (EF006901) | 0 |
| Number of input ranges 0 mV ... 500 mV (EF006904) | 0 |
| Number of input ranges 0 V ... 1 V (EF006890) | 0 |
| Number of input ranges 0 V ... 2 V (EF006894) | 0 |
| Number of input ranges 0 V ... 2.5 V (EF006895) | 0 |
| Number of input ranges 0 V ... 5 V (EF006903) | 0 |
| Number of input ranges 0 V ... 10 V (EF006892) | 0 |
| Number of input ranges 0 V ... 20 V (EF006897) | 0 |
| Number of input ranges 0 V ... 24 V (EF006899) | 0 |
| Number of input ranges 0 V ... 30 V (EF006900) | 0 |
| Number of input ranges 1 V ... 5 V (EF006907) | 0 |
| Number of input ranges 2 V ... 10 V (EF006914) | 0 |
| Number of input ranges +5 V ... -5 V (EF006889) | 0 |
| Number of input ranges +10 V ... -10 V (EF006888) | 0 |
| Number of input ranges 5 V ... 0 V (EF006924) | 0 |
| Number of input ranges 5 V ... 1 V (EF006925) | 0 |
| Number of input ranges 10 V ... 0 V (EF006910) | 0 |
| Number of input ranges 10 V ... 2 V (EF006911) | 0 |
| Number of input ranges 0 mA ... 5 mA (EF006902) | 0 |
| Number of input ranges 0 mA ... 10 mA (EF006891) | 0 |
| Number of input ranges 0 mA ... 20 mA (EF006896) | 0 |
| Number of input ranges 4 mA ... 20 mA (EF006921) | 1 |
| Number of input ranges -5 mA ... +5 mA (EF006922) | 0 |
| Number of input ranges -10 mA ... +10 mA (EF006908) | 0 |
| Number of input ranges -20 mA ... +20 mA (EF006916) | 0 |
| Number of input ranges 20 mA ... 0 mA (EF006918) | 0 |
| Number of input ranges 20 mA ... 4 mA (EF006919) | 0 |
| Number of output ranges -60 mV ... +60 mV (EF006880) | 0 |
| Number of output ranges -100 mV ... +100 mV (EF006865) | 0 |
| Number of output ranges -300 mV ... +300 mV (EF006873) | 0 |
| Number of output ranges -500 mV ... +500 mV (EF006879) | 0 |
| Number of output ranges -1 V ... +1 V (EF006859) | 0 |
| Number of output ranges -2 V ... +2 V (EF006866) | 0 |
| Number of output ranges -2.5 V ... +2.5 V (EF006868) | 0 |
| Number of output ranges -5 V ... +5 V (EF006876) | 0 |
| Number of output ranges -10 V ... +10 V (EF006862) | 0 |
| Number of output ranges -20 V ... +20 V (EF006870) | 0 |
| Number of output ranges 0 mV ... 60 mV (EF006858) | 0 |
| Number of output ranges 0 mV ... 100 mV (EF006846) | 0 |
| Number of output ranges 0 mV ... 200 mV (EF006851) | 0 |
| Number of output ranges 0 mV ... 300 mV (EF006854) | 0 |
| Number of output ranges 0 mV ... 500 mV (EF006857) | 0 |
| Number of output ranges 0 V ... 1 V (EF006843) | 0 |
| Number of output ranges 0 V ... 2 V (EF006847) | 0 |
| Number of output ranges 0 V ... 2.5 V (EF006848) | 0 |
| Number of output ranges 0 V ... 5 V (EF006856) | 0 |
| Number of output ranges 0 V ... 10 V (EF006845) | 0 |
| Number of output ranges 0 V ... 20 V (EF006850) | 0 |
| Number of output ranges 0 V ... 24 V (EF006852) | 0 |
| Number of output ranges 0 V ... 30 V (EF006853) | 0 |
| Number of output ranges 1 V ... 5 V (EF006860) | 1 |
| Number of output ranges 2 V ... 10 V (EF006867) | 0 |
| Number of output ranges +5 V ... -5 V (EF006842) | 0 |
| Number of output ranges +10 V ... -10 V (EF006841) | 0 |
| Number of output ranges 5 V ... 0 V (EF006877) | 0 |
| Number of output ranges 5 V ... 1 V (EF006878) | 0 |
| Number of output ranges 10 V ... 0 V (EF006863) | 0 |
| Number of output ranges 10 V ... 2 V (EF006864) | 0 |
| Number of output ranges 0 mA ... 5 mA (EF006855) | 0 |
| Number of output ranges 0 mA ... 10 mA (EF006844) | 0 |
| Number of output ranges 0 mA ... 20 mA (EF006849) | 0 |
| Number of output ranges 4 mA ... 20 mA (EF006874) | 2 |
| Number of output ranges -5 mA ... +5 mA (EF006875) | 0 |
| Number of output ranges -10 mA ... +10 mA (EF006861) | 0 |
| Number of output ranges -20 mA ... +20 mA (EF006869) | 0 |
| Number of output ranges 20 mA ... 0 mA (EF006871) | 0 |
| Number of output ranges 20 mA ... 4 mA (EF006872) | 0 |
| Number of channels (EF000259) | 1 |
| Malfunction message output (EF007499) | No |
| Inherently safe according to EN 60947-5-6 NAMUR (EF007112) | Yes |
| Galvanic separation between inputs (EF007224) | No |
| Height (EF000040) | 107.9 mm |
| Width (EF000008) | 17.5 mm |
| Depth (EF000049) | 113.7 mm |
| Power consumption (EF000346) | 2.2 W |
| Load (EF007096) | 600 Ohm |
| Operating temperature (EF002393) | -40 °C |
| Temperature drift (EF007507) | 0.01 %/K |
| Construction type of device (EF007276) | Built-in device |
| Type of electric connection (EF003961) | Other |
| Mounting method (EF000003) | Snap mounting support rail |
| Degree of protection (IP) (EF005474) | IP20 |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOG PHOENIX INTERFACE TECHNOLOGY AND SWITCHING DEVICES EN.pdf | 29 Mbytes |
|
| PHOENIX CONTACT-2924029-MACX MCR-EX-SL-RPSSI-I-UP-SP | 150 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.