ILB DN 24 DI16 DO16 2862602 PHOENIX CONTACT Inline Block IO digital input/output module, DeviceNet™, 16 inpu.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

ILB DN 24 DI16 DO16 2862602 PHOENIX CONTACT Inline Block IO digital input/output module, DeviceNet™, 16 inpu..

ILB DN 24 DI16 DO16

2862602

PHOENIX_CONTACT

Available

Ship on today

Inline Block IO digital input/output module, DeviceNet™, 16 inputs, 24 V DC, 2, 3-wire connection technology, 16 outputs, 24 V DC, 500 mA, 2, 3-wire connection technology

More details


Programmable Logic Controllers Plcs

AUTOMATION Industrial Automation - PHOENIX CONTACT

I/O systems. Connectors - PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
1+$387.13
2+$376.03
3+$370.71
4+$370.57
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Width156 mm
Height141 mm
Depth57 mm
Note on dimensionsSpecfications with connectors

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)85 % (non-condensing)
Permissible humidity (storage/transport)95 % (non-condensing)
Air pressure (operation)80 kPa ... 108 kPa (up to 2000 m above mean sea level)
Air pressure (storage/transport)66 kPa ... 108 kPa (up to 3500 m above mean sea level)
Degree of protectionIP20

General

Net weight500 g
Note on weight specificationswith connectors
Mounting typeDIN rail
NS 35/7,5

Interfaces

Fieldbus systemDeviceNet™
DesignationDeviceNet™
Connection method2x 5-pos. TWIN-COMBICON connectors
Transmission speed125 kBit/s ... 500 kBit/s
Number of positions5

Power supply for module electronics

Supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply current70 mA
Current consumptionapprox. 25 mA

Digital inputs

Input nameDigital inputs
Connection methodSpring-cage connection
2, 3-wire
Number of inputs16 (EN 61131-2 type 1)
Typical response timeapprox. 500 µs
Protective circuitShort-circuit protection, overload protection of the sensor supply
Input voltage24 V DC
Input voltage range "0" signal-30 V DC ... 5 V DC
Input voltage range "1" signal15 V DC ... 30 V DC
Nominal input current at UIN5 mA

Digital outputs

Output nameDigital outputs
Connection methodSpring-cage connection
2, 3-wire
Number of outputs16
Protective circuitShort-circuit and overload protection
Output voltage24 V DC
Nominal output voltage24 V DC
Maximum output current per channel500 mA
Maximum output current per module / terminal block8 A
Maximum output current per module8 A
Nominal load, inductive12 VA
Nominal load, lamp12 W
Nominal load, ohmic12 W

Datasheet - PDF

Title: Language: Size: Type:
PHOENIX CONTACT-2862602-ILB DN 24 DI16 DO16 English 167 Kbytes PHOENIX CONTACT-2862602-ILB DN 24 DI16 DO16

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.