I/O extension module
Radioline: I/O expansion module, 4 digital relay outputs (5 A, 250 V AC/DC)
PLC's > Fieldbus, decentr. periphery - digital I/O module
Safety
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Orderkey | 2901536 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 461 (C-6-2017) |
| GTIN | 4046356610483 |
| Weight per Piece (excluding packing) | 179.400 g |
| Custom tariff number | 85177000 |
| Country of origin | DE (Germany) |
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 70 °C (>55°C derating) |
| -40 °F ... 158 °F (>131°F derating) | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| -40 °F ... 185 °F | |
| Permissible humidity (operation) | 20 % ... 85 % |
| Permissible humidity (storage/transport) | 20 % ... 85 % |
| Altitude | 2000 m |
| Vibration (operation) | in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
| Shock | 16g, 11 ms |
| Overvoltage category | II |
|---|---|
| Mounting position | any |
| Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
| Degree of pollution | 2 |
| Housing material | PA 6.6-FR |
| Flammability rating according to UL 94 | V0 |
| MTTF | 1087 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
| 523 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) | |
| 204 Years (Telcordia standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) |
| Supply voltage range | 19.2 V DC ... 30.5 V DC (DIN rail connector) |
|---|---|
| Max. current consumption | ≤ 55 mA (At 24 V DC, at 25°C) |
| Transient surge protection | Yes |
| Number of outputs | 4 |
|---|---|
| Contact type | PDT |
| Contact material | AgSnO2 |
| Maximum switching voltage | 250 V AC/DC |
| Min. switching current | ≥ 10 mA |
| Max. switching current | 5 A (per channel) |
| Mechanical service life | 1x 107cycles |
| Electrical service life | 1x 105cycles (At 5 A, 250 V AC, ohmic) |
| 2x 105cycles (At 2 A, 250 V AC, cosφ 0.4) | |
| 2x 105cycles (At 1 A, 24 V DC, L/R = 48 ms) | |
| Maximum switching frequency | 2 Hz |
| Switching capacity | 120 W (24 V DC) |
| 120 W (30 V DC) | |
| 20 W (48 V DC) | |
| 18 W (60 V DC) | |
| 22 W (110 V DC) | |
| 40 W (220 V DC) | |
| 42 W (250 V DC) | |
| 1250 VA | |
| Behavior of the outputs (adjustable via DIP switch) | Hold / Reset |
| Digital I/O | 300 V (Rated insulation voltage (in each case between the digital outputs // TBUS supply, reinforced insulation according to EN 61010)) |
|---|
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 7 mm |
| Tightening torque | 0.6 Nm |
| Screw thread | M3 |
| Status display | Green LED (supply voltage, PWR) |
|---|---|
| Green LED (bus communication, DAT) | |
| Red LED (periphery error, ERR) | |
| Yellow LED (digital output, DO1) | |
| Yellow LED (digital output, DO2) | |
| Yellow LED (digital output, DO3) | |
| Yellow LED (digital output, DO4) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Standard designation | EMC Directive 2014/30/EU |
| Standards/regulations | EN 61000-6-2 |
| Standard designation | EMC Directive 2014/30/EU |
| Standards/regulations | EN 61000-6-4 |
| Standard designation | Ex Directive (ATEX) |
| Standards/regulations | EN 60079-0 |
| Standard designation | Ex Directive (ATEX) |
| Standards/regulations | EN-60079-15 |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 |
| Flammability rating according to UL 94 | V0 |
| Shock | 16g, 11 ms |
| Vibration (operation) | in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA nC IIC T4 Gc |
| IECEx | Ex nA nC IIC T4 Gc |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T4A | |
| Class I, Zone 2, IIC T4 | |
| Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Feature Name | Feature Value |
|---|---|
| Supply voltage DC (EF007534) | 19.2 V |
| Voltage type (supply voltage) (EF002991) | DC |
| Number of digital inputs (EF001992) | 0 |
| Number of digital outputs (EF001993) | 4 |
| Digital inputs configurable (EF008516) | No |
| Digital outputs configurable (EF008520) | No |
| Type of voltage (input voltage) (EF003033) | DC |
| Type of digital output (EF003601) | Relay |
| Output current (EF003202) | 5 A |
| Short-circuit protection, outputs available (EF003203) | No |
| Number of HW-interfaces industrial Ethernet (EF003020) | 0 |
| Number of interfaces PROFINET (EF006932) | 0 |
| Number of HW-interfaces RS-232 (EF003021) | 0 |
| Number of HW-interfaces RS-422 (EF003022) | 0 |
| Number of HW-interfaces RS-485 (EF003023) | 0 |
| Number of HW-interfaces serial TTY (EF003024) | 0 |
| Number of HW-interfaces parallel (EF003026) | 0 |
| Number of HW-interfaces wireless (EF006933) | 0 |
| Number of HW-interfaces USB (EF003025) | 0 |
| Number of HW-interfaces other (EF003027) | 0 |
| With optical interface (EF003028) | Yes |
| Radio standard Bluetooth (EF007178) | No |
| Radio standard WLAN 802.11 (EF007179) | No |
| Radio standard GPRS (EF008523) | No |
| Radio standard GSM (EF008524) | No |
| Radio standard UMTS (EF008525) | No |
| IO link master (EF007298) | No |
| System accessory (EF004118) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |
| Type of electric connection (EF003961) | Screw connection |
| Time delay at signal change (EF002382) | 0 ms |
| Fieldbus connection over separate bus coupler possible (EF004002) | Yes |
| Suitable for rail mounting (EF003972) | Yes |
| Wall mounting/direct mounting (EF007020) | No |
| Front built-in possible (EF007016) | No |
| Rack-assembly possible (EF007018) | No |
| Suitable for safety functions (EF001597) | No |
| SIL according to IEC 61508 (EF009889) | None |
| Performance level according to EN ISO 13849-1 (EF007399) | None |
| Appendant operation agent (Ex ia) (EF004141) | No |
| Appendant operation agent (Ex ib) (EF004142) | No |
| Explosion safety category for gas (EF003997) | None |
| Explosion safety category for dust (EF003998) | None |
| Width (EF000008) | 17.6 mm |
| Height (EF000040) | 113.01416 mm |
| Depth (EF000049) | 113.6 mm |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE AUTOMATION PHOENIX EN.pdf | 35 Mbytes |
|
| PHOENIX CONTACT-2901536-RAD-DOR4-IFS | 938 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.