Key Commercial Data

Orderkey2901535
Packing unit1 pc
Catalog pagePage 460 (C-6-2017)
GTIN4046356610490
Weight per Piece (excluding packing)163.200 g
Custom tariff number85177000
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width17.5 mm
Height113 mm
Depth114.5 mm
Dimensional drawing

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 70 °C
-40 °F ... 158 °F
Ambient temperature (storage/transport)-40 °C ... 85 °C
-40 °F ... 185 °F
Permissible humidity (operation)20 % ... 85 %
Permissible humidity (storage/transport)20 % ... 85 %
Altitude2000 m
Vibration (operation)in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz
Shock16g, 11 ms

General

Overvoltage categoryII
Mounting positionany
Assembly instructionson standard DIN rail NS 35 in accordance with EN 60715
Degree of pollution2
Housing materialPA 6.6-FR
Flammability rating according to UL 94V0
MTTF1766 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day))
653 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day))
250 Years (Telcordia standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day))

Supply

Supply voltage range19.2 V DC ... 30.5 V DC (DIN rail connector)
Max. current consumption≤ 11 mA (At 24 V DC, at 25°C)
Transient surge protectionYes

Digital inputs

Description of the inputDigital input
Number of inputs4
Switching level "1" signal10 V AC/DC ... 50 V AC/DC (Low-voltage input)
50 V AC/DC ... 250 V AC/DC (High-voltage input)
Switching level "0" signal0 V AC/DC ... 4 V AC/DC (Low-voltage input)
0 V AC/DC ... 20 V AC/DC (High-voltage input)
Input frequency≤ 2 Hz
Min. voltage input signal0 V AC/DC
Max. voltage input signal250 V AC/DC

Electrical isolation

Digital I/O300 V (Rated insulation voltage (in each case between the digital inputs // TBUS supply, reinforced insulation according to EN 61010))

Test voltage

Digital I/O2.5 kV AC (50 Hz, 1 min.)

Connection data

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length7 mm
Tightening torque0.6 Nm
Screw threadM3

Status indicator

Status displayGreen LED (supply voltage, PWR)
Green LED (bus communication, DAT)
Red LED (periphery error, ERR)
Yellow LED (digital input, DI1)
Yellow LED (digital input, DI2)
Yellow LED (digital input, DI3)
Yellow LED (digital input, DI4)

Standards and Regulations

Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Standard designationEMC Directive 2014/30/EU
Standards/regulationsEN 61000-6-2
Standard designationEMC Directive 2014/30/EU
Standards/regulationsEN 61000-6-4
Standard designationEx Directive (ATEX)
Standards/regulationsEN 60079-0
Standard designationEx Directive (ATEX)
Standards/regulationsEN-60079-15
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2
Flammability rating according to UL 94V0
Shock16g, 11 ms
Vibration (operation)in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc
IECExEx nA IIC T4 Gc
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T4A
Class I, Zone 2, IIC T4
Noxious gas testISA-S71.04-1985 G3 Harsh Group A

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Articles in set

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.