IBS RL 24 DIO 4/2/4-LK 2819985 PHOENIX CONTACT Distributed I/O device View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

IBS RL 24 DIO 4/2/4-LK 2819985 PHOENIX CONTACT Distributed I/O device

IBS RL 24 DIO 4/2/4-LK

2819985

PHOENIX_CONTACT

Distributed I/O device

More details


I/O

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2819985
Packing unit1 pc
Catalog pagePage 237 (C-6-2017)
GTIN4017918188665
Weight per Piece (excluding packing)650.000 g
Custom tariff number85176200
Country of originDE (Germany)

Note

Utilization restriction1

Dimensions

Width127 mm
Height67 mm
Depth71 mm
Note on dimensionsWith bus connectors and mounting plate

Ambient conditions

Ambient temperature (operation)0 °C ... 55 °C
Ambient temperature (storage/transport)-25 °C ... 70 °C
Permissible humidity (operation)100 %
Permissible humidity (storage/transport)95 % (non-condensing)
Air pressure (operation)860 hPa ... 1080 hPa (up to 1500 m above sea level)
Air pressure (storage/transport)660 hPa ... 1080 hPa (up to 3500 m above sea level)
Degree of protectionIP65/IP67
NoteSeal unused slots/connections to ensure the degree of protection.

General

Mounting typeWall mounting
Net weight650 g
Note on weight specificationswithout plug or mounting plate
NoteSeal unused slots/connections to ensure the degree of protection.

Interfaces

DesignationINTERBUS
Connection methodOptic fiber (polymer fiber 980/1000 µm)
Transmission speed500 kbps
Transmission physicsFO

Power supply for module electronics

Supply voltage24 V DC
Supply voltage range18.5 V DC ... 32 V DC (including ripple)
RippleMax 3.6 VSSwithin the permissible voltage range
Supply currenttyp. 80 mA (plus sensor current)

Digital inputs

Input nameDigital inputs
Connection technology2, 3, 4-wire
Number of inputs4
Type of protectionElectronic short-circuit/overload protection for each group
Input voltage range "0" signal0 V DC ... 5 V DC
Input voltage range "1" signal11 V DC ... 30 V DC
Typical input current per channel3 mA
Delay at signal change from 0 to 13 ms
Delay at signal change from 1 to 03 ms

Digital outputs

Output nameDigital outputs
Connection technology2, 3-wire
Number of outputs2
Type of protectionElectronic short-circuit/overload protection for each channel
Output voltage24 V DC
Nominal output voltage24 V
Maximum output current per channel500 mA
Nominal load, inductive12 VA (1.2 H, 48 Ω)
Nominal load, lamp12 W
Nominal load, ohmic12 W

Electrical isolation

Test sectionBetween bus logic and outputs 500 V AC 50 Hz 1 min.

Standards and Regulations

Connection in acc. with standardCUL

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.