Key Commercial Data

Orderkey2800125
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 20 (TT-2011)
GTIN4046356481281
Weight per Piece (excluding packing)707.900 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height95 mm
Width70.4 mm
Depth65.7 mm
Horizontal pitch4 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 85 °C
Permissible humidity (operation)≤ 95 %

General

IEC power supply systemTT
TN-S
Housing materialPA-GF
Flammability rating according to UL 94V0
Colorblack
Standards for cearances and creepage distancesEN 60664-1
EN 61643-11
Mounting typeDIN rail: 35 mm
TypeDIN rail module, one-piece
Number of positions4
Surge protection fault messageoptical
Direction of action3L-N & N-PE

Protective circuit

IEC test classificationI
T1
EN typeT1
Maximum continuous operating voltage UC260 V AC
Maximum continuous operating voltage UC(L-N)260 V AC
Maximum continuous operating voltage UC(N-PE)260 V AC
UT(TOV-proof)335 V (5 sec /L-N)
UT(TOV-safe)1200 V AC (200 ms / N-PE)
Nominal frequency fN50 Hz
60 Hz
Residual current IPE≤ 0.1 mA
Standby power consumption PC≤ 26 mVA
Max. discharge current Imax(8/20) µs maximum (L-N)35 kA
Max. discharge current Imax(8/20) µs maximum (N-PE)50 kA
Impulse discharge current (10/350) µs, charge17.5 As
Impulse discharge current (10/350) µs, specific energy306 kJ/Ω (L-N)
Impulse discharge current (10/350) µs, peak value limp35 kA (L-N)
Nominal discharge current In(8/20) µs
Nominal discharge current In(8/20) µs (L-N)35 kA
Nominal discharge current In(8/20) µs (N-PE)50 kA
Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-N)≤ 2 kV
Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE)≤ 2 kV
Voltage protection level Up(L-N)≤ 2 kV
Voltage protection level Up(N-PE)≤ 2 kV
Response time tA≤ 100 ns
Response time tA(L-N)≤ 100 ns
Response time tA(N-PE)≤ 100 ns
Max. backup fuse with branch wiring400 A (NH-gL)
Short-circuit withstand capability IPwith max. backup fuse (r.m.s.)25 kA
Follow current interrupt rating Ifi(L-N)3 kA
Follow current quenching capacity Ifi(N-PE)100 A

Connection, protective circuit

Connection methodScrew connection
Connection method INBiconnect screw terminal block
Connection method OUTBiconnect screw terminal block
Connection technologyBiconnect terminal block
Screw threadM5
Tightening torque4.5 Nm
Stripping length14.5 mm
Conductor cross section flexible min.0.5 mm²
Conductor cross section flexible max.25 mm²
Conductor cross section solid min.0.5 mm²
Conductor cross section solid max.35 mm²
Conductor cross section AWG min.20
Conductor cross section AWG max.2

Standards and Regulations

Standards/regulationsIEC 61643-1 2005
DIN EN 61643-11 2002
DIN EN 61643-11/A11 2007

Classifications


Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.