Inline function terminal
Inline, Coupler terminal block, for expansion of the local bus Inline, transmission rate on the local bus: 500 kBit/s / 2 MBit/s, protection index: IP20, including inline connectors and marking fields
Inline, Coupler terminal, for extending the Inline local bus, transmission speed in the local bus: 500 kbps / 2 Mbps, degree of protection: IP20, including Inline connectors and marking fields
PLC's > Fieldbus, decentr. periphery - communication module
I/O
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Dimensional drawing | ![]() |
| Width | 48.8 mm |
| Height | 135 mm |
| Depth | 71.5 mm |
| Note on application | |
| Note on application | Only for industrial use |
| Inline local bus | |
| Number of interfaces | 1 (incoming local bus) |
| Connection method | Inline shield connector |
| Note on the connection method | Standard INTERBUS cable |
| Transmission speed | 500 kbps / 2 Mbps (Can be used in Inline stations with these transmission speeds) |
| Transmission physics | Copper |
| Inline local bus | |
| Number of interfaces | 1 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps / 2 Mbps |
| System limits | |
| Number of local bus devices that can be connected | max. 63 (without additional power terminal block, observe allowable total current consumption) |
| Number of devices with parameter channel | 63 |
| Module | |
| ID code (hex) | none |
| Input address area | 0 Byte |
| Output address area | 0 Byte |
| Register length | 0 bit |
| Required parameter data | 0 Byte |
| Required configuration data | 0 Byte |
| Product type | I/O component |
| Product family | Inline |
| Type | modular |
| Scope of delivery | including Inline connectors and marking fields |
| Special properties | for extending the Inline local bus |
| Data management status | |
| Article revision | 06 |
| Maximum power dissipation for nominal condition | 1.45 W |
| Protective circuit | Surge protection (segment supply, main supply, 24 V supply); Input protective diodes (can be destroyed by permanent overload)Pulse loads up to 1500 W are short circuited by the input protective diode. |
| Protection against polarity reversal (segment supply/main supply); Parallel diodes for protection against polarity reversal; in the event of an error the high current flowing through the diodes causes the fuse connected upstream to blow. | |
| Polarity reversal (24 V supply); Serial diode in the lead path of the power supply unit; in the event of an error only a low current flows. In the event of an error, no fuse trips within the external power supply unit. | |
| Short-circuit protection of the communications power; electronic | |
| Short-circuit protection of the analog supply; electronic | |
| Potentials: 24 V supply (U24V) for generating ULand UANA | |
| Supply voltage | 24 V DC (via Inline connector) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 1.25 A (at nominal voltage; consisting of: 0.75 A DC for the communications power and 0.5 A DC for the analog voltage supply) |
| min. 60 mA (without connected Inline I/O terminals) | |
| Potentials: Communications power (UL) | |
| Supply voltage | 7.5 V DC |
| Potentials: Supply of analog modules (UANA) | |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Potentials: Main circuit supply (UM) | |
| Supply voltage | 24 V DC (via Inline connector) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Potentials: Segment circuit supply (US) | |
| Supply voltage | 24 V DC (via Inline connector) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: 5 V supply incoming local bus / 7.5 V communications power, 24 V analog power supply, 24 V power supply for generating voltages ULand UANA | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 5 V supply incoming local bus / 24 V main supply, 24 V segment supply | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 7.5 V communications power, 24 V analog power supply, 24 V power supply for generating voltages ULand UANA/ functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 7.5 V communications power, 24 V analog power supply, 24 V power supply for generating voltages ULand UANA/ 24 V main supply, 24 V segment supply | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 24 V main supply, 24 V segment supply, 24 V power supply for generating voltages ULand UANA/ functional ground | 500 V AC, 50 Hz, 1 min. |
| Connection technology | |
| Connection name | Inline connector |
| Conductor connection | |
| Connection method | Spring-cage connection |
| Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
| Inline connector | |
| Connection method | Spring-cage connection |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| Degree of protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Mounting type | DIN rail mounting |
| Feature Name | Feature Value |
|---|---|
| Supply voltage DC (EF007534) | 19.2 V |
| Voltage type (supply voltage) (EF002991) | DC |
| Radio standard Bluetooth (EF007178) | No |
| Radio standard WLAN 802.11 (EF007179) | No |
| Radio standard GPRS (EF008523) | No |
| IO link master (EF007298) | No |
| System accessory (EF004118) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |
| With potential separation (EF003272) | No |
| Fieldbus connection over separate bus coupler possible (EF004002) | Yes |
| Suitable for rail mounting (EF003972) | Yes |
| Wall mounting/direct mounting (EF007020) | No |
| Front built-in possible (EF007016) | No |
| Rack-assembly possible (EF007018) | No |
| Suitable for safety functions (EF001597) | No |
| Performance level according to EN ISO 13849-1 (EF007399) | None |
| Appendant operation agent (Ex ia) (EF004141) | No |
| Appendant operation agent (Ex ib) (EF004142) | No |
| Explosion safety category for gas (EF003997) | None |
| Explosion safety category for dust (EF003998) | None |
| Width (EF000008) | 48.6 mm |
| Height (EF000040) | 136.044074 mm |
| Depth (EF000049) | 70.510188 mm |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOG PHOENIX AUTOMATION EN.pdf | 35 Mbytes |
|
| PHOENIX CONTACT-2897457-IB IL 24 LSKIP-PAC | 115 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.