Surge protection base element
PT plug-in protection base element with protection circuit for two two-conductor signal circuits without earth potential, gas discharger between connections 3-4 (GND) and 9-10, mounting on NS 35/7.5 and NS 35/15, housing width: 17.5 mm

Categories:

  • Earthing, lightning and surge protection > Accessories/spare parts for surge protection data networks/MCR-technology
  • PHOENIX CONTACT > Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 74,70 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

MORE INFO

Key Commercial Data

Orderkey2839224
Packing unit10 pc
Catalog pagePage 99 (C-4-2017)
GTIN4017918182762
Weight per Piece (excluding packing)58.200 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height90 mm
Width17.7 mm
Depth51.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorjet black RAL 9005
Standards for cearances and creepage distancesVDE 0110-1
Mounting typeDIN rail: 35 mm
TypeBase element, DIN rail mounting
Number of positions4
Direction of actionSignal Ground/Shield-Earth Ground

Protective circuit

Nominal voltage UN24 V AC
24 V DC
Maximum continuous voltage UC40 V DC
28 V AC
Rated current450 mA (45°C)
Resistance in series2.2 Ω ±10 %
Surge protection fault messagenone
Max. required back-up fuse500 mA (T)

Connection data

Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Standards and Regulations

Standards/specificationsIEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21 2001 + A1:2009 + A2:2013

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

DATASHEET - PDF

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.