Product successfully added to your shopping cart
CN-UB/E-BB
2817686
PHOENIX_CONTACT
1
Surge protection device
Trabtech (TT)
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Orderkey | 2817686 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 177 (C-4-2017) |
GTIN | 4017918148584 |
Weight per Piece (excluding packing) | 117.260 g |
Custom tariff number | 85363010 |
Country of origin | DE (Germany) |
Housing material | Aluminum |
---|---|
Color | black |
Standards for cearances and creepage distances | DIN VDE 0110-1 |
IEC 60664-1 | |
Overvoltage category | II |
Degree of pollution | 2 |
Mounting type | Connection-specific intermediate plugging |
Type | Attachment plug |
Direction of action | Line-Shield/Earth Ground |
IEC test classification | C2 |
---|---|
C3 | |
D1 | |
VDE requirement class | C2 |
C3 | |
D1 | |
Maximum continuous voltage UC | 180 V DC |
130 V AC | |
Maximum continuous voltage UC(line-earth) | 180 V DC |
130 V AC | |
Rated current | 5 A (25 °C) |
Operating effective current ICat UC | ≤ 1 µA |
Residual current IPE | ≤ 2 µA |
Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
Nominal discharge current In(8/20) µs (line-shield) | 5 kA |
Nominal discharge current In(8/20) µs (shield-earth) | 5 kA |
Total discharge current Itotal(8/20) µs | 10 kA |
Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 470 V |
Output voltage limitation at 1 kV/µs (line-shield) spike | ≤ 590 V |
Output voltage limitation at 1 kV/µs (shield-earth) spike | ≤ 470 V |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 470 V |
≤ 33 V | |
Output voltage limitation at 1 kV/µs (shield-earth) static | ≤ 33 V |
Residual voltage at In(line-earth) | ≤ 160 V (1.5 m cable) |
Residual voltage at In(line-shield) | ≤ 55 V |
Residual voltage at In(shield-earth) | ≤ 160 V (1.5 m cable) |
Voltage protection level Up(line-earth) | ≤ 500 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up(line-shield) | ≤ 700 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up(shield-ground) | ≤ 500 V (C2 - 10 kV / 5 kA) |
Response time tA(line-earth) | ≤ 100 ns |
Response time tA (line-shield) | ≤ 100 ns |
Response time tA (shield-earth) | ≤ 100 ns |
Input attenuation aE, asym. | 0.1 dB (≤ 100 MHz) |
Cut-off frequency fg (3 dB), asym. (shield) in 50 Ohm system | typ. 1 GHz |
Standing wave ratio SWR in a 50 Ω system | ≤ 1.2 (200 MHz) |
Permissible HF power Pmaxat VSWR = xx (50 ohm system) | 300 W (at SWR = 1.1 in a 50 Ω system) |
80 W (VSWR = ∞) | |
Capacity asymmetrical (shield) | 7 pF (typical) |
Surge protection fault message | none |
Impulse durability (line-earth) | C2 - 10 kV/5 kA |
D1 - 2.5 kA | |
Impulse durability (shield-earth) | C2 - 10 kV / 5 kA |
D1 - 2.5 kA |
Connection method | N connector 50 Ω |
---|---|
Connection method IN | N connector, female |
Connection method OUT | N connector, female |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX PROTECTION EN.pdf | 27 Mbytes | |
PHOENIX CONTACT-2817686-CN-UB/E-BB | 99 Kbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.