Product successfully added to your shopping cart
CN-UB/E
2763691
PHOENIX_CONTACT
1
Surge protection device
Zwischenstecker mit Überspannungsschutz für koaxiale Signalschnittstellen mit erdpotentialfreiem Schirm. Anschluss: N-Connector Buchse-Stecker
Trabtech (TT)
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Orderkey | 2763691 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 177 (C-4-2017) |
| GTIN | 4017918099527 |
| Weight per Piece (excluding packing) | 154.500 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
| Ambient temperature (operation) | -40 °C ... 80 °C |
|---|---|
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
| Housing material | Aluminum |
|---|---|
| Overvoltage category | II |
| Degree of pollution | 2 |
| Mounting type | Connection-specific intermediate plugging |
| Type | Attachment plug |
| Direction of action | Line-Shield/Earth Ground |
| Note | To meet the discharge conditions for DC voltages, please note the following information: "The surge protective device should be used together with a transmitter unit, which shuts down in the event of a short-circuit." |
|---|
| IEC test classification | C2 |
|---|---|
| C3 | |
| D1 | |
| Maximum continuous voltage UC | 180 V DC |
| 130 V AC | |
| Rated current | 5 A (25 °C) |
| Operating effective current ICat UC | ≤ 1 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Nominal discharge current In(8/20) µs (line-shield) | 5 kA |
| Nominal discharge current In(8/20) µs (shield-earth) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 2.5 kA |
| Pulse discharge current Iimp(10/350) µs (line-shield) | 2.5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 470 V |
| Output voltage limitation at 1 kV/µs (line-shield) spike | ≤ 590 V |
| Output voltage limitation at 1 kV/µs (shield-earth) spike | ≤ 470 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 33 V |
| Output voltage limitation at 1 kV/µs (line-shield) static | ≤ 33 V |
| Output voltage limitation at 1 kV/µs (shield-earth) static | ≤ 33 V |
| Residual voltage at In(line-earth) | ≤ 160 V (1.5 m cable) |
| Residual voltage at In(line-shield) | ≤ 55 V |
| Residual voltage at In(shield-earth) | ≤ 160 V (1.5 m cable) |
| Voltage protection level Up(line-earth) | ≤ 500 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up(line-shield) | ≤ 700 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up(shield-ground) | ≤ 500 V (C2 - 10 kV / 5 kA) |
| Response time tA | ≤ 100 ns |
| Input attenuation aE, asym. | typ. 0.1 dB (≤ 100 MHz/50 Ω) |
| Cut-off frequency fg (3 dB), asym. (shield) in 50 Ohm system | typ. 1 GHz |
| Standing wave ratio SWR in a 50 Ω system | typ. 1.2 (≤ 200 MHz) |
| Permissible HF power Pmaxat VSWR = xx (50 ohm system) | 300 W (VSWR = 1.1) |
| 80 W (VSWR = ∞) | |
| Capacity asymmetrical (shield) | typ. 7 pF |
| Surge protection fault message | none |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| C3 - 100 A | |
| D1 - 2.5 kA | |
| Impulse durability (line-shield) | C2 - 10 kV/5 kA |
| C3 - 100 A | |
| D1 - 2.5 kA |
| Connection method | N connector 50 Ω |
|---|---|
| Connection method IN | N socket |
| Connection method OUT | N plug |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOG PHOENIX PROTECTION EN .pdf | 27 Mbytes |
|
| PHOENIX CONTACT-2763691-CN-UB/E | 135 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.