Attachment plug with replaceable surge protection for coaxial signal interfaces. Connection: N connector plug/socket

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection for transceiver systems - PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
1+$115.03
4+$103.91
8+$100.27
11+$98.91
15+$97.79
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Height25 mm
Width25 mm
Depth72 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 80 °C

General

Housing materialNickel-plated brass
Colornickel
Overvoltage categoryIII
Pollution degree2
Mounting typeConnection-specific intermediate plugging
TypeAttachment plug
Direction of actionLine-Shield/Earth Ground

Protective circuit

IEC test classificationC1
C2
C3
D1
Maximum continuous voltage UC280 V DC
195 V AC
Nominal current IN5 A AC (25 °C)
Operating effective current IC at UC≤ 1 µA
Nominal discharge current In (8/20) µs (Core-Earth)20 kA
Nominal discharge current In (8/20) µs (Core-Shield)20 kA
Pulse discharge current Iimp (10/350) µs (core-ground)2.5 kA
Pulse discharge current Iimp (10/350) µs (core-shield)2.5 kA
Total surge current (8/20) µs20 kA
Total surge current (10/350) µs2.5 kA
Max. discharge current Imax (8/20) µs maximum (Core-Earth)20 kA
Max. discharge current Imax (8/20) µs maximum (Core-Shield)20 kA
Nominal pulse current Ian (10/1000) µs (Core-Earth)100 A
Nominal pulse current Ian (10/1000) µs (Core-Shield)100 A
Impulse discharge current (10/350)˽µs, peak value limp2.5 kA
Output voltage limitation at 1 kV/µs (Core-Earth) spike≤ 900 V
Output voltage limitation at 1 kV/µs (Core-Shield) spike≤ 900 V
Voltage protection level Up (core-ground)≤ 900 V (C1 - 1 kV/500 A)
≤ 1.1 kV (C2 - 10 kV / 5 kA)
≤ 1 kV (C3 - 25 A)
Voltage protection level Up (core-shield)≤ 900 V (C1 - 1 kV/500 A)
≤ 1.1 kV (C2 - 10 kV / 5 kA)
≤ 1 kV (C3 - 25 A)
Response time tA≤ 100 ns
Input attenuation aE, asym.typ. 0.1 dB (≤ 1.2 GHz / 50 Ω)
typ. 0.2 dB (≤ 2.2 GHz / 50 Ω)
Cut-off frequency fg (3 dB), asym. (shield) in 50 Ohm systemtyp. 3 GHz
Standing wave ratio SWR in a 50 Ω systemtyp. 1.1 (≤ 2 GHz)
Permissible HF power Pmax at VSWR = xx (50 ohm system)700 W (VSWR = 1.1)
200 W (VSWR = ∞)
Capacitytyp. 1.5 pF
Impulse durability (conductor-ground)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 100 A
D1 - 2,5 kA
Impulse durability (conductor-shield)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 100 A
D1 - 2.5 kA

Connection data

Connection methodN connector 50 Ω
Connection type INN connector, male
Connection type OUTN connector, female

Datasheet - PDF

Title: Language: Size: Type:
PHOENIX CONTACT-2818148-CN-UB-280DC-SB English 122 Kbytes PHOENIX CONTACT-2818148-CN-UB-280DC-SB

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.