Product successfully added to your shopping cart
IB IL TEMP 2 UTH-PAC
2861386
PHOENIX_CONTACT
1
Inline terminal
Inline, Temperature recording module, Analogue UTH inputs: 2 (Thermocouples or linear voltage), connection technology: 2 conductors, transmission rate on local bus: 500 kBit/s, protection rating: IP20, including Inline connector and marking surface
Inline, Temperature measurement terminal, Analog UTH inputs: 2 (Thermocouples or linear voltage), connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
PLC's > Fieldbus, decentr. periphery - analogue I/O module
I/O
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Dimensional drawing | ![]() |
| Width | 12.2 mm |
| Height | 136.8 mm |
| Depth | 71.5 mm |
| Note on dimensions | Housing dimensions |
| Note on application | |
| Note on application | Only for industrial use |
| Utilization restriction | |
| CCCex note | Use in potentially explosive areas is not permitted in China. |
| Inline local bus | |
| Number of interfaces | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
| Module | |
| ID code (dec.) | 127 |
| ID code (hex) | 7F |
| Length code (hex) | 02 |
| Length code (dec) | 02 |
| Process data channel | 32 bit |
| Input address area | 4 Byte |
| Output address area | 4 Byte |
| Register length | 32 bit |
| Required parameter data | 6 Byte |
| Required configuration data | 4 Byte |
| Analog | |
| Input name | Analog UTH inputs |
| Description of the input | Inputs for thermocouples or linear voltage |
| Number of inputs | 2 (Thermocouples or linear voltage) |
| Connection method | Inline connector |
| Connection technology | 2-conductor |
| Note regarding the connection technology | Shielded compensating line for TC with encapsulated sensors |
| A/D conversion time | typ. 120 µs (per channel) |
| Sensor types that can be used (TC) | U, T, L, J, E, K, N, S, R, B, C, W, HK |
| Measuring principle | Successive approximation |
| Measured value representation | 16 bits (15 bits + sign bit) |
| Process data update | max. 30 ms (For both channels) |
| Protective circuit | Surge protection (TC channels); up to ±40 V |
| Product type | I/O component |
| Product family | Inline |
| Type | modular |
| Scope of delivery | including Inline connector and labeling field |
| Operating mode | Process data operation with 2 words |
| Diagnostics messages | Failure of the internal I/O supply I/O error message sent to the bus coupler |
| Failure of or insufficient communications power ULI/O error message sent to the bus coupler | |
| I/O error Error message in the process data | |
| User error Error message in the process data | |
| Data management status | |
| Article revision | 11 |
| Insulation characteristics | |
| Overvoltage category | II (IEC 60664-1, EN 60664-1) |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
| Maximum power dissipation for nominal condition | 0.9 W |
| Potentials: Communications power (UL) | |
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current draw | max. 60 mA |
| typ. 43 mA | |
| Potentials: Supply of analog modules (UANA) | |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 18 mA |
| typ. 11 mA | |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: 7.5 V supply (bus logics)/24 V analog supply (analog I/O) | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 7.5 V supply (bus logic)/functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 24 V analog supply (analog I/O)/functional ground | 500 V AC, 50 Hz, 1 min. |
| Connection technology | |
| Connection name | Inline connector |
| Conductor connection | |
| Connection method | Spring-cage connection |
| Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
| Inline connector | |
| Connection method | Spring-cage connection |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| Degree of protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Mounting type | DIN rail mounting |
| Feature Name | Feature Value |
|---|---|
| Supply voltage DC (EF007534) | 19.2 V |
| Voltage type (supply voltage) (EF002991) | DC |
| Input, current (EF003204) | No |
| Input, voltage (EF003205) | No |
| Input, resistor (EF003206) | No |
| Input, resistance thermometer (EF003207) | No |
| Input, thermocouple (EF003208) | Yes |
| Input signal, configurable (EF003209) | No |
| Output, current (EF003212) | No |
| Output, voltage (EF003213) | No |
| Output signal configurable (EF003214) | No |
| Number of analogue inputs (EF001994) | 0 |
| Number of analogue outputs (EF001995) | 0 |
| Analogue inputs configurable (EF008518) | No |
| Analogue outputs configurable (EF008519) | No |
| Number of HW-interfaces industrial Ethernet (EF003020) | 0 |
| Number of interfaces PROFINET (EF006932) | 0 |
| Number of HW-interfaces RS-232 (EF003021) | 0 |
| Number of HW-interfaces RS-422 (EF003022) | 0 |
| Number of HW-interfaces RS-485 (EF003023) | 0 |
| Number of HW-interfaces serial TTY (EF003024) | 0 |
| Number of HW-interfaces parallel (EF003026) | 0 |
| Number of HW-interfaces wireless (EF006933) | 0 |
| Number of HW-interfaces USB (EF003025) | 0 |
| Number of HW-interfaces other (EF003027) | 0 |
| Supporting protocol for EtherCAT (EF017564) | No |
| Supporting protocol for TCP/IP (EF003050) | No |
| Supporting protocol for PROFIBUS (EF003052) | No |
| Supporting protocol for CAN (EF003053) | No |
| Supporting protocol for INTERBUS (EF003054) | No |
| Supporting protocol for ASI (EF003051) | No |
| Supporting protocol for KNX (EF003055) | No |
| Supporting protocol for Modbus (EF003057) | No |
| Supporting protocol for Data-Highway (EF003058) | No |
| Supporting protocol for DeviceNet (EF003059) | No |
| Supporting protocol for SUCONET (EF003060) | No |
| Supporting protocol for LON (EF003017) | No |
| Supporting protocol for PROFINET IO (EF007525) | No |
| Supporting protocol for PROFINET CBA (EF007524) | No |
| Supporting protocol for SERCOS (EF006657) | No |
| Supporting protocol for Foundation Fieldbus (EF007522) | No |
| Supporting protocol for EtherNet/IP (EF007521) | No |
| Supporting protocol for AS-Interface Safety at Work (EF007519) | No |
| Supporting protocol for DeviceNet Safety (EF007520) | No |
| Supporting protocol for INTERBUS-Safety (EF006662) | No |
| Supporting protocol for PROFIsafe (EF007526) | No |
| Supporting protocol for SafetyBUS p (EF007527) | No |
| Supporting protocol for other bus systems (EF003062) | Yes |
| Radio standard Bluetooth (EF007178) | No |
| Radio standard WLAN 802.11 (EF007179) | No |
| Radio standard GPRS (EF008523) | No |
| Radio standard GSM (EF008524) | No |
| Radio standard UMTS (EF008525) | No |
| IO link master (EF007298) | No |
| System accessory (EF004118) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |
| Type of electric connection (EF003961) | Other |
| Fieldbus connection over separate bus coupler possible (EF004002) | Yes |
| Suitable for rail mounting (EF003972) | Yes |
| Wall mounting/direct mounting (EF007020) | Yes |
| Front built-in possible (EF007016) | No |
| Rack-assembly possible (EF007018) | No |
| Suitable for safety functions (EF001597) | No |
| Performance level according to EN ISO 13849-1 (EF007399) | None |
| Appendant operation agent (Ex ia) (EF004141) | No |
| Appendant operation agent (Ex ib) (EF004142) | No |
| Explosion safety category for gas (EF003997) | None |
| Explosion safety category for dust (EF003998) | None |
| Width (EF000008) | 12.15 mm |
| Height (EF000040) | 138.44 mm |
| Depth (EF000049) | 70.51 mm |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOG PHOENIX AUTOMATION EN.pdf | 35 Mbytes |
|
| PHOENIX CONTACT-2861386-IB IL TEMP 2 UTH-PAC | 123 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.