MINI MCR-SL-UI-UI-SP-NC 2864163 PHOENIX CONTACT MCR 3-way isolating amplifier, I/O can be configured via DIP.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MINI MCR-SL-UI-UI-SP-NC 2864163 PHOENIX CONTACT MCR 3-way isolating amplifier, I/O can be configured via DIP..

MINI MCR-SL-UI-UI-SP-NC

2864163

PHOENIX_CONTACT

Available

Ship on today

MCR 3-way isolating amplifier, I/O can be configured via DIP switches, for the electrical isolation of analog signals, with spring-cage connection, standard configuration

More details


Converters

INTERFACE Signal converters, switching devices, and power supply units - PHOENIX CONTACT

Modular Converter MCR technique. Analog - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+183,73 €
2+179,18 €
3+176,93 €
4+175,50 €
5+175,49 €
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Width6.2 mm
Height93.1 mm
Depth102.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 65 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Degree of protectionIP20

Input data

Number of inputs1
Configurable/programmableYes, unconfigured
Voltage input signal0 V ... 10 V
0 V ... 5 V
1 V ... 5 V
2 V ... 10 V
Current input signal0 mA ... 20 mA
4 mA ... 20 mA
Max. input voltage30 V
Max. input current50 mA
Input resistance of voltage inputapprox. 100 kΩ
Input resistance current inputapprox. 50 Ω

Output data

Number of outputs1
Configurable/programmableYes, unconfigured
Voltage output signal0 V ... 10 V
0 V ... 5 V
1 V ... 5 V
2 V ... 10 V
Current output signal0 mA ... 20 mA (please indicate if different setting when ordering)
4 mA ... 20 mA
Max. output voltageapprox. 12.5 V
Max. output current28 mA
Short-circuit currentapprox. 22 mA
Load/output load voltage output≥ 10 kΩ
Load/output load current output< 500 Ω (at 20 mA)

Power supply

Nominal supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Max. current consumption< 19 mA (Current output, at 24 V DC incl. load)
< 9 mA (Voltage output, at 24 V DC incl. load)
Power consumption< 450 mW (Current output)
< 200 mW (Voltage output)

Connection data

Connection methodSpring-cage connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Stripping length8 mm

General

No. of channels1
Maximum transmission error≤ 0.1 % (of final value)
< 0.4 % (Without adjustment)
Maximum temperature coefficient< 0.01 %/K
Temperature coefficient, typical< 0.002 %/K
Limit frequency (3 dB)approx. 100 Hz
Step response (10-90%)approx. 3.2 ms
Protective circuitTransient protection
Electrical isolationBasic insulation according to EN 61010
Overvoltage categoryII
Pollution degree2
Rated insulation voltage50 V AC/DC
Test voltage, input/output/supply1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibilityConformance with EMC Directive 2004/108/EC
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Colorgreen
Housing materialPBT
Mounting positionany
Assembly instructionsThe T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
ConformanceCE-compliant
ATEXEx II 3 G Ex nA IIC T4 Gc X
UL, USA / CanadaUL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
GLGL EMC 2 D

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value5 %
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value5 %
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value5 %

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2864163-MINI MCR-SL-UI-UI-SP-NCEnglish149 KbytesPHOENIX CONTACT-2864163-MINI MCR-SL-UI-UI-SP-NC