Product successfully added to your shopping cart
MINI MCR-SL-UI-I-LP-SP-NC
2902830
PHOENIX_CONTACT
1
Signal conditioner
INTERFACE Components (IF)
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Orderkey | 2902830 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 102 (C-7-2015) |
GTIN | 4046356681865 |
Weight per Piece (excluding packing) | 74.400 g |
Custom tariff number | 85437090 |
Country of origin | DE (Germany) |
Ambient temperature (operation) | -25 °C ... 70 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Number of inputs | 1 |
---|---|
Voltage input signal | 0 mV ... 1000 mV |
0 mV ... 750 mV | |
0 mV ... 500 mV | |
0 mV ... 300 mV | |
0 mV ... 250 mV | |
0 mV ... 200 mV | |
0 mV ... 150 mV | |
0 mV ... 125 mV | |
0 mV ... 120 mV | |
0 mV ... 100 mV | |
0 mV ... 75 mV | |
0 mV ... 60 mV | |
0 mV ... 50 mV | |
0 V ... 10 V | |
0 V ... 7.5 V | |
0 V ... 5 V | |
0 V ... 3 V | |
0 V ... 2.5 V | |
0 V ... 2 V | |
0 V ... 1.5 V | |
0 V ... 1.25 V | |
0 V ... 1.2 V | |
0 V ... 30 V | |
0 V ... 25 V | |
0 V ... 20 V | |
0 V ... 12.5 V | |
0 V ... 12 V | |
0 V ... 15 V | |
-1000 mV ... 1000 mV | |
-750 mV ... 750 mV | |
-500 mV ... 500 mV | |
-300 mV ... 300 mV | |
-250 mV ... 250 mV | |
-200 mV ... 200 mV | |
-125 mV ... 125 mV | |
-120 mV ... 120 mV | |
-150 mV ... 150 mV | |
-100 mV ... 100 mV | |
-75 mV ... 75 mV | |
-60 mV ... 60 mV | |
-50 mV ... 50 mV | |
-10 V ... 10 V | |
-7.5 V ... 7.5 V | |
-5 V ... 5 V | |
-3 V ... 3 V | |
-2.5 V ... 2.5 V | |
-2 V ... 2 V | |
-1.25 V ... 1.25 V | |
-1.2 V ... 1.2 V | |
-1.5 V ... 1.5 V | |
-30 V ... 30 V | |
-25 V ... 25 V | |
-20 V ... 20 V | |
-12.5 V ... 12.5 V | |
-12 V ... 12 V | |
-15 V ... 15 V | |
200 mV ... 1000 mV | |
150 mV ... 750 mV | |
100 mV ... 500 mV | |
60 mV ... 300 mV | |
50 mV ... 250 mV | |
40 mV ... 200 mV | |
25 mV ... 125 mV | |
24 mV ... 120 mV | |
30 mV ... 150 mV | |
20 mV ... 100 mV | |
15 mV ... 75 mV | |
12 mV ... 60 mV | |
10 mV ... 50 mV | |
2 V ... 10 V | |
1.5 V ... 7.5 V | |
1 V ... 5 V | |
0.6 V ... 3 V | |
0.5 V ... 2.5 V | |
0.4 V ... 2 V | |
0.25 V ... 1.25 V | |
0.24 V ... 1.2 V | |
0.3 V ... 1.5 V | |
6 V ... 30 V | |
5 V ... 25 V | |
4 V ... 20 V | |
2.5 V ... 12.5 V | |
2.4 V ... 12 V | |
3 V ... 15 V | |
Current input signal | 0 mA ... 40 mA |
0 mA ... 30 mA | |
0 mA ... 20 mA | |
0 mA ... 12 mA | |
0 mA ... 10 mA | |
0 mA ... 8 mA | |
0 mA ... 7.5 mA | |
0 mA ... 5 mA | |
0 mA ... 6 mA | |
0 mA ... 4 mA | |
0 mA ... 3 mA | |
0 mA ... 2.5 mA | |
0 mA ... 2 mA | |
-40 mA ... 40 mA | |
-30 mA ... 30 mA | |
-20 mA ... 20 mA | |
-12 mA ... 12 mA | |
-10 mA ... 10 mA | |
-8 mA ... 8 mA | |
-7.5 mA ... 7.5 mA | |
-5 mA ... 5 mA | |
-6 mA ... 6 mA | |
-4 mA ... 4 mA | |
-3 mA ... 3 mA | |
-2.5 mA ... 2.5 mA | |
-2 mA ... 2 mA | |
8 mA ... 40 mA | |
6 mA ... 30 mA | |
4 mA ... 20 mA | |
2.4 mA ... 12 mA | |
2 mA ... 10 mA | |
1.6 mA ... 8 mA | |
1.5 mA ... 7.5 mA | |
1 mA ... 5 mA | |
1.2 mA ... 6 mA | |
0.8 mA ... 4 mA | |
0.6 mA ... 3 mA | |
0.5 mA ... 2.5 mA | |
0.4 mA ... 2 mA | |
max. input voltage | < 40 V |
Max. input current | < 50 mA (Dielectric strength up to 30 V) |
Input resistance of voltage input | approx. 100 kΩ (At ≤ 1 V, otherwise approximately 1 MΩ) |
Input resistance current input | ≤ 50 Ω |
Number of outputs | 1 |
---|---|
Configurable/programmable | Yes, preconfigured |
Current output signal | 4 mA ... 20 mA |
Max. output current | 35 mA (output limit) |
Load/output load current output | < 1000 Ω ((UB- 8 V) / 22 mA) |
Ripple | < 20 mVPP(at 500 Ω) |
Supply voltage range | no separate supply voltage necessary |
---|---|
Power consumption | 28 mW (without signal) |
Connection method | Spring-cage connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Stripping length | 8 mm |
No. of channels | 1 |
---|---|
Maximum transmission error | < 0.1 % (of final value) |
< 0.2 % (Without adjustment) | |
Maximum temperature coefficient | 0.01 %/K |
Temperature coefficient, typical | 0.005 %/K |
Limit frequency (3 dB) | approx. 30 Hz |
Alignment zero | ± 2 % |
Alignment span | ± 2 % |
Step response (10-90%) | approx. 16 ms |
Electrical isolation | Basic insulation according to EN 61010 |
Overvoltage category | II |
Degree of pollution | 2 |
Rated insulation voltage | 50 V AC/DC |
Test voltage input/output | 1.5 kV (50 Hz, 1 min.) |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Color | green |
Housing material | PBT |
Mounting position | any |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Listed |
Class I, Div. 2, Groups A, B, C, D T5 | |
Class I, Zone 2, Group IIC | |
Certificate of classification | DNV GL 14085-15HH |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Designation | Electromagnetic RF field |
---|---|
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 0.5 % |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 2 % |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 0.5 % |
Electromagnetic compatibility | Conformance with EMC directive |
---|---|
Noise emission | EN 61000-6-4 |
Standards/regulations | EN 61000-4-2 |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
EN 61000-4-4 | |
Comments | Criterion B |
Standards/regulations | EN 61000-4-5 |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Electrical isolation | Basic insulation according to EN 61010 |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Listed |
Class I, Div. 2, Groups A, B, C, D T5 | |
Class I, Zone 2, Group IIC | |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Title: | Size: | Type: |
---|---|---|
PHOENIX CONTACT-2902830-MINI MCR-SL-UI-I-LP-SP-NC | 117 Kbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.