PHOENIX CONTACT  UPS-BAT/VRLA/24DC/38AH 2320335 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

UPS-BAT/VRLA/24DC/38AH 2320335 PHOENIX CONTACT Energy storage

Reference: UPS-BAT/VRLA/24DC/38AH

Code: 2320335

Manufacturer: PHOENIX CONTACT

Description:

Energy storage
Energy storage, lead AGM, VRLA technology, 24 V DC, 38 Ah, automatic detection and communication with QUINT UPS-IQ

Categories:

  • PHOENIX CONTACT > Power Supplies (PS)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

LAST VIEWED

MORE INFO

Key Commercial Data

Orderkey2320335
Packing unit1 pc
Catalog pagePage 287 (C-4-2017)
GTIN4046356599061
Weight per Piece (excluding packing)25,300.000 g
Custom tariff number85072080
Country of originCN (China)

Dimensions

Width330 mm
Height221 mm
Depth197 mm

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)0 °C ... 40 °C
Ambient temperature (storage/transport)0 °C ... 40 °C
Max. permissible relative humidity (operation)95 %
Degree of pollution2

Input data

Nominal input voltage24 V DC
Buffer period72 min. (20 A)
35 min. (40 A)

Output data

Nominal output voltage24 V DC
Output current Imax45 A
Connection in seriesNo
Output fuse2x 25 A ATOF 32V

General

IQ technologyYes
DisposalUsed batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. They can also be returned to Phoenix Contact or the manufacturer.
Net weight26 kg
Memory mediumLead rechargeable battery module
Protection classIII
Degree of protectionIP20
Mounting positionhorizontally, on a mounting plate

Standards and Regulations

Connection in acc. with standardCUL
Standard - Electrical safetyEN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)
Shipbuilding approvalDNV GL (EMC A), ABS
UL approvalsUL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
VdS approvalG 100002
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
15 Hz ... 150 Hz, 2.3g, 90 min.

Classifications

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.