PHOENIX CONTACT  QUINT-ORING/24DC/2X10/1X20 2320173 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

QUINT-ORING/24DC/2X10/1X20 2320173 PHOENIX CONTACT Redundancy module, with protective coating

Reference: QUINT-ORING/24DC/2X10/1X20

Code: 2320173

Manufacturer: PHOENIX CONTACT

Description:

Redundancy module, with protective coating
QUINT active redundancy module for rail mounting with ACB (Auto Current Balancing) technology and monitoring functions, 24 V DC input, 24 V DC/2 x 10 A or 1 x 20 A output, incl. universal adapter for mounted UTA 107/30 rail

Categories:

  • Low-voltage industrial components > Surge protection module
  • PHOENIX CONTACT > Power Supplies (PS)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • ETIM
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 277,56 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

Key Commercial Data

Orderkey2320173
Packing unit1 pc
Catalog pagePage 260 (C-4-2017)
GTIN4046356524902
Weight per Piece (excluding packing)400.000 g
Custom tariff number85049091
Country of originCN (China)

Dimensions

Width32 mm
Height130 mm
Depth125 mm
Width with alternative assembly122 mm
Height with alternative assembly130 mm
Depth with alternative assembly35 mm

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested)-40 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Max. permissible relative humidity (operation)≤ 100 % (at 25 °C, non-condensing)
Climatic class3K3 (in acc. with EN 60721)
Degree of pollution2
Installation height2000 m

Input data

Nominal input voltage range24 V DC
Input voltage range18 V DC ... 28 V DC (SELV)
Nominal input current2x 10 A (-25 °C ... 60 °C)
1x 20 A (-25 °C ... 60 °C)
Maximum input current2x 15 A (-25°C ... 40°C)
1x 30 A (-25°C ... 40°C)
60 A (12 ms, SFB Technology)

Output data

Nominal output voltage0.1 V (< DC input)
Nominal output current (IN)20 A (Increasing power)
10 A (Redundancy)
Derating60 °C ... 70 °C (2.5%/K)
Connection in seriesNo
Output overvoltage protection≤ 32 V DC
Power loss nominal load max.2 W (IOUT= 20 A)

General

Net weight0.4 kg
Efficiency> 98 %
Protection classIII
Degree of protectionIP20
MTBF (IEC 61709, SN 29500)
> 1000000 h (40 °C)
Mounting positionhorizontal DIN rail NS 35, EN 60715
Assembly instructionsalignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom

Connection data, input

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.14
Conductor cross section AWG max.12
Stripping length8 mm
Screw threadM3

Connection data, output

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.6 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.4 mm²
Conductor cross section AWG min.10
Stripping length7 mm
Screw threadM3

Connection data for signaling

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.16
Conductor cross section AWG max.12
Stripping length10 mm
Screw threadM3

Standards and Regulations

Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Noise immunityEN 61000-6-2:2005
Connection in acc. with standardCUL
Standards/regulationsEN 61000-4-2
Contact discharge4 kV (Test Level 2)
Standards/regulationsEN 61000-4-3
Frequency range80 MHz ... 1 GHz
Test field strength10 V/m (Test Level 3)
Frequency range1.4 GHz ... 2 GHz
Test field strength3 V/m (Test Level 2)
Standards/regulationsEN 61000-4-4
CommentsCriterion B
Standards/regulationsEN 61000-6-3
EN 61000-4-6
Frequency range0.15 MHz ... 80 MHz
Voltage10 V (Test Level 3)
Low Voltage DirectiveConformance with Low Voltage Directive 2006/95/EC
Standard - Electrical safetyEN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltageIEC 60950-1 (SELV) and EN 60204-1 (PELV)
UL approvalsUL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g tv= 90 min.
Noxious gas testISA-S71.04-1985 G3 Harsh Group A
ATEX II 3 G Ex nA IIC T4 Gc
DEKRA 11ATEX0031 X
IECExEx nA IIC T4 Gc
IECEx DEK 11.0015X

Classifications

ETIM for 2320173 Low-voltage industrial controls and switchgear (EC000683)

Feature nameFunction (EF000030)
Feature valueOther
Feature nameVoltage type (operating voltage) (EF005294)
Feature valueDC
Feature nameOperating voltage DC (EF008208)
Feature value18 V
Feature nameWith LED indication (EF005950)
Feature valueYes

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.