PHOENIX CONTACT  MINI MCR-2-SPS-24-15 1033202 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

MINI MCR-2-SPS-24-15 1033202 PHOENIX CONTACT Constant voltage source

Reference: MINI MCR-2-SPS-24-15

Code: 1033202

Manufacturer: PHOENIX CONTACT

Description:

Constant voltage source
Constant voltage source with plug-in connection technology for generating a very precise constant voltage of 15 V and for the supply of sensors without their own supply. Screw connection technology.

Categories:

  • Low-voltage industrial components > Accessories/spare parts for low-voltage switch technology
  • PHOENIX CONTACT > INTERFACE Components (IF)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • ETIM
  • Reviews
Guarantee, repair and return.

Unit Price: 124,71 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

Key Commercial Data

Orderkey1033202
Packing unit1 pc
NoteMade to Order (non-returnable)
GTIN4055626537962
Weight per Piece (excluding packing)106.720 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width6.2 mm
Height110.5 mm
Depth120.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C

Input data

Voltage input signal9.6 V DC ... 30 V DC
Transmitter supply voltage15 V

Output data

Max. output voltage15 V DC
Output voltage with wire break15 V
Output current≤ 30 mA
Short-circuit current> 35 mA
Ripple< 20 mVPP(at 600 Ω)

Power supply

Supply voltage range9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption< 38.2 mA (24 V)
< 79.8 mA (12 V)
Power consumption< 900 mW (9.6 V DC)

Connection data

Connection methodScrew connection
Single conductor/terminal point, solid, with ferrule, min.0.2 mm²
Single conductor/terminal point, solid, with ferrule, max.1.5 mm²
Single conductor/terminal point, solid, without ferrule, min.0.2 mm²
Single conductor/terminal point, solid, without ferrule, max.2.5 mm²
Min. AWG conductor cross section, flexible24
Max. AWG conductor cross section, flexible12
Stripping length10 mm
Screw threadM3

General

Maximum transmission error≤ 0.4 % (of final value)
Maximum temperature coefficient< 0.01 %/K
Electrical isolationReinforced insulation in accordance with IEC 61010-1
Overvoltage categoryII
Degree of pollution2
Rated insulation voltage300 V (effective)
Test voltage, input/output/supply3 kV (50 Hz, 1 min.)
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Colorgray
Housing materialPBT
Mounting positionany
Assembly instructionsThe T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Electrical isolationReinforced insulation in accordance with IEC 61010-1
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
DNV GL-TemperatureB
DNV GL-HumidityB
DNV GL-VibrationA
DNV GL-EMCA
DNV GL-EnclosureRequired protection according to the Rules shall be provided upon installation on board
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

ETIM for 1033202 Low-voltage industrial controls and switchgear (EC002498)

Feature nameType of accessory/spare part (EF000215)
Feature valueOther
Feature nameAccessory (EF013236)
Feature valueYes
Feature nameSpare part (EF013237)
Feature valueNo

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.