PHOENIX CONTACT  MINI MCR-2-CVCS 2902064 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

MINI MCR-2-CVCS 2902064 PHOENIX CONTACT Constant voltage source

Reference: MINI MCR-2-CVCS

Code: 2902064

Manufacturer: PHOENIX CONTACT

Description:

Constant voltage source
Constant voltage/current supply with plug-in connection technology, input voltage 9.6 V DC ... 30 V DC. Output voltage: 1.25 V ... 10 V DC or output current: adjustable to 2.5 mA... 20 mA. 10VDC oder Ausgangsstrom: 2.5mA ... 20mA and instellbar. Configurable via DIP switch. Screw connection technology.

Categories:

  • Low-voltage industrial components > Accessories/spare parts for low-voltage switch technology
  • PHOENIX CONTACT > INTERFACE Components (IF)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 160,23 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

MORE INFO

Key Commercial Data

Orderkey2902064
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 100 (C-5-2017)
GTIN4046356652124
Weight per Piece (excluding packing)107.100 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width6.2 mm
Height110.5 mm
Depth120.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C

Input data

Voltage input signal9.6 V DC ... 30 V DC
Transmitter supply voltage10 V

Output data

Configurable/programmableYes
Max. output voltage10 V DC
8.75 V DC
7.5 V DC
6.25 V DC
5 V DC
3.75 V DC
2.5 V DC
1.25 V DC
Max. output current20 mA
17.5 mA
15 mA
12.5 mA
10 mA
7.5 mA
5 mA
2.5 mA
Output voltage with wire break13.5 V
Output current≤ 30 mA
Short-circuit current> 32 mA
Load/output load current output≤ 600 Ω (20 mA)
Ripple< 20 mVPP(at 600 Ω)

Power supply

Supply voltage range9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption< 42 mA (24 V DC)
< 85 mA (12 V DC)
Power consumption< 1.1 W (9.6 V DC)

Connection data

Connection methodScrew connection
Single conductor/terminal point, solid, with ferrule, min.0.2 mm²
Single conductor/terminal point, solid, with ferrule, max.1.5 mm²
Single conductor/terminal point, solid, without ferrule, min.0.2 mm²
Single conductor/terminal point, solid, without ferrule, max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Min. AWG conductor cross section, flexible24
Max. AWG conductor cross section, flexible12
Stripping length10 mm
Screw threadM3

General

Maximum transmission error≤ 0.1 % (of final value)
Maximum temperature coefficient< 0.01 %/K
Electrical isolationReinforced insulation in accordance with IEC 61010-1
Overvoltage categoryII
Degree of pollution2
Rated insulation voltage300 V (effective)
Test voltage, input/output/supply3 kV (50 Hz, 1 min.)
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Colorgray
Housing materialPBT
Mounting positionany
Assembly instructionsThe T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Electrical isolationReinforced insulation in accordance with IEC 61010-1
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
DNV GL-TemperatureB
DNV GL-HumidityB
DNV GL-VibrationA
DNV GL-EMCA
DNV GL-EnclosureRequired protection according to the Rules shall be provided upon installation on board
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.