PHOENIX CONTACT  PT-BE/FM 2839282 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

PT-BE/FM 2839282 PHOENIX CONTACT Type 3 surge protection base element

Reference: PT-BE/FM

Code: 2839282

Manufacturer: PHOENIX CONTACT

Description:

Type 3 surge protection base element
Base element for PT plug-in protection, mounting on NS 35/7.5 and NS 35/15, housing width: 17.5 mm

Categories:

  • Earthing, lightning and surge protection > Surge protection device for data networks/MCR-technology
  • PHOENIX CONTACT > Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 39,38 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

MORE INFO

Key Commercial Data

Orderkey2839282
Packing unit10 pc
Catalog pagePage 114 (C-4-2017)
GTIN4017918182502
Weight per Piece (excluding packing)45.910 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height90 mm
Width17.7 mm
Depth51.2 mm
Horizontal pitch1 Div.
Complete module height90 mm
Complete module width17.7 mm
Complete module depth65.5 mm

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 150 Hz/20 cycles/axis/X, Y, Z)

General

EN typeT3
Number of portsOne
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPA 6.6-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeBase element, DIN rail mounting
Number of positions3
Surge protection fault messageRemote indication contact

Protective circuit

Nominal voltage UN230 V AC (TN-S)
230 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC264 V AC
Rated load current IL26 A (30 °C)
Short-circuit current rating ISCCR1.5 kA AC
Max. backup fuse with branch wiringdepends on the plug used
Maximum backup fuse for through wiring25 A (gG / B / C)

Indicator/remote signaling

Switching functionN/C contact
Connection methodScrew connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm

Connection data

Connection methodScrew connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm

UL specifications

SPD TypeACC
Nominal voltage240 V DC
Rated load current IL20 A
Power distribution systemSplit phase
Nominal frequency50/60 Hz

UL indicator/remote signaling

Tightening torque5 lbf-in. ... 7 lbf-in.
Conductor cross section AWG14 ... 12

UL connection data

Conductor cross section AWG14 ... 12
Tightening torque5 lbf-in. ... 7 lbf-in.

Standards and Regulations

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

DATASHEET - PDF

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.