PHOENIX CONTACT  IB ST 24 AI 4/SF 2754309 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

IB ST 24 AI 4/SF 2754309 PHOENIX CONTACT I/O module

Reference: IB ST 24 AI 4/SF

Code: 2754309

Manufacturer: PHOENIX CONTACT

Description:

I/O module

Categories:

  • PHOENIX CONTACT

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

Go to successor article:IB ST 24 AI 4/EF2700838

Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

LAST VIEWED

MORE INFO

Key Commercial Data

Orderkey2754309
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 250 (C-8-2013)
GTIN4017918063061
Weight per Piece (excluding packing)600.000 g
Custom tariff number85389091

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width118 mm
Height117 mm
Length116 mm

Interfaces

InterfaceST local bus
Connection methodST local bus connector
Transmission speed500 kbps
Transmission physicsCopper

Power supply

Communications power UL9 V DC (from the ST local bus)
Typical current consumption65 mA (without passive sensors)
Max. current consumption125 mA (without passive sensors)
I/O voltage± 24 V DC 5 % (ripple)
I/O voltage range20 V DC ... 30 V DC
Max. power consumption from the local bus150 mA (from the ST local bus)
120 mA (from the ST local bus)

Electrical isolation

Test sectionBus/Inputs 500 V AC 50 Hz 1 min.
Supply voltage/inputs 500 V AC 50 Hz 1 min.
Supply voltage/Ground conductor 500 V AC 50 Hz 1 min.
I/O voltage/Ground conductor 500 V AC 50 Hz 1 min.

Inputs

No. of channels4
Note on the number of channelsdifferential inputs, voltage or current
Connection technology2, 3, 4-wire
Voltage input signal0 V ... 10 V
Input resistance of voltage input> 200 kΩ
Voltage input quantization2.44 mV
Basic error limit0.05 %
Current input signal0 mA ... 20 mA
Input resistance current input50 Ω
Current input quantization4.88 µA
Basic error limit0.05 %
Measuring principleSuccessive approximation
Measured value monitoring to the PLCAll channels simultaneously
Measured value representation16 bit two's complement
Measured value resolution12 bits
A/D conversion time10 µs (per channel)
Process data update0.75 ms (per channel/3 ms all channels)
Limit frequency (3 dB)58.5 Hz

General

Weight600 g
Mounting typeDIN rail

Standards and Regulations

Connection in acc. with standardCUL

Classifications

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.