PHOENIX CONTACT  VAL-MS 1000DC-PV-ST 2800624 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-MS 1000DC-PV-ST 2800624 PHOENIX CONTACT Type 2 surge protection plug

Reference: VAL-MS 1000DC-PV-ST

Code: 2800624

Manufacturer: PHOENIX CONTACT

Description:

Type 2 surge protection plug
Replacement plug-in protection for PV arrester combinations from the VAL-MS 1000DC-PV product line-...

Categories:

  • Earthing, lightning and surge protection > Accessories/spare parts for surge protection power supply systems
  • PHOENIX CONTACT > Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 64,80 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

MORE INFO

Key Commercial Data

Orderkey2800624
Packing unit1 pc
Catalog pagePage 65 (C-4-2017)
GTIN4046356615099
Weight per Piece (excluding packing)68.600 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height52.4 mm
Width17.5 mm
Depth55.3 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)60g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)7.5g (5-500 Hz/2.5 h/XYZ)

General

IEC test classificationPV II
PV T2
EN typeT2
SPD failure behaviorOCM (Open-circuit mode)
Installation locationInside
AccessibilityAccessible
Installation location of the disconnect deviceInternal
Mounting typeon base element
Colorjet black RAL 9005
Housing materialPA 6.6-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Surge protection fault messageoptical

Protective circuit DC voltage side (DC)

Maximum continuous operating voltage UCPV585 V DC
Short-circuit current rating ISCPV2000 A
Continuous operating current ICPV< 20 µA
Standby power consumption PC≤ 25 mVA
Nominal discharge current (8/20) µs15 kA
Maximum discharge current Imax(8/20) µs40 kA
Voltage protection level Up≤ 1.9 kV
Residual voltage Ures≤ 1.9 kV (at In)
≤ 1.5 kV (at 5 kA)
≤ 1.7 kV (at 10 kA)
≤ 2 kV (at 20 kA)
≤ 2.3 kV (at 30 kA)
≤ 2.5 kV (at 40 kA)
Response time tA≤ 25 ns
Insulation resistance Riso> 5 GΩ (at 500 V DC)

Connection data

Connection methodpluggable

UL specifications

SPD Type1CA
Maximum continuous operating voltage MCOV1170 V DC
Nominal voltage1170 V DC
Mode of protection(L+) - (L-)
(L+) - G
(L-) - G
Power distribution systemDC PV
Voltage protection rating VPR3 kV
Nominal discharge current In10 kA
Short-circuit current rating (SCCR)50 kA

Standards and Regulations

Standards/regulationsEN 50539-11 2013

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.