PHOENIX CONTACT  CN-LAMBDA/4-2.25-SB 2801056 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

CN-LAMBDA/4-2.25-SB 2801056 PHOENIX CONTACT Surge protection device

Reference: CN-LAMBDA/4-2.25-SB

Code: 2801056

Manufacturer: PHOENIX CONTACT

Description:

Surge protection device
Adapter with Lambda/4 technology as surge protection for coaxial signal interfaces. Connection: N male-female connectors

Categories:

  • Earthing, lightning and surge protection > Surge protection device for data networks/MCR-technology
  • PHOENIX CONTACT > Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 123,92 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

MORE INFO

Key Commercial Data

Orderkey2801056
Packing unit1 pc
Catalog pagePage 178 (C-4-2017)
GTIN4046356678247
Weight per Piece (excluding packing)260.000 g
Custom tariff number85363010
Country of originCN (China)

Dimensions

Height77.5 mm
Width25 mm
Length81.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Altitude2000 m
Degree of protectionIP68

General

Housing materialHPb59-1
Colornickel
Standards for cearances and creepage distancesIEC 60664-1
Mounting typeConnection-specific intermediate plugging
TypeAttachment plug
Number of positions1
Direction of actionLine-Shield/Earth Ground

Protective circuit

IEC test classificationC2
C3
D1
VDE requirement classC2
C3
D1
Nominal current IN5 A (25 °C)
Nominal discharge current In(8/20) µs (line-earth)50 kA
Nominal discharge current In(8/20) µs (line-shield)50 kA
Total surge current (8/20) µs60 kA
Total surge current (10/350) µs20 kA
Max. discharge current Imax(8/20) µs maximum (line-earth)60 kA
Max. discharge current Imax(8/20) µs maximum (line-shield)60 kA
Impulse discharge current (10/350) µs, peak value limp≤ 20 kA
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 1 V
Output voltage limitation at 1 kV/µs (line-shield) spike≤ 1 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 1 V
Voltage protection level Up(line-earth)≤ 15 V (6 kV / 3 kA)
≤ 5 V (C1 - 1 kV/500 A)
≤ 25 V (C2 - 10 kV / 5 kA)
Voltage protection level Up(line-shield)≤ 25 V (C2 - 10 kV / 5 kA)
≤ 5 V (C1 - 1 kV/500 A)
≤ 15 V (6 kV / 3 kA)
Input attenuation aE, asym.≤ 0.2 dB (50 Ω)
Frequency range0.8 GHz ... 2.25 GHz
Standing wave ratio SWR in a 50 Ω systemtyp. 1.2
max. 1.25
Permissible HF power Pmaxat VSWR = xx (50 ohm system)≤ 500 W
≤ 4 kW (peak)
Surge protection fault messagenone
Impulse durability (line-earth)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
D1 - 2.5 kA

Connection data

Connection methodN connector 50 Ω
Connection method INN connector, male
Connection method OUTN connector, female

Standards and Regulations

Standards/specificationsIEC 61643-21/A1 2008
EN 61643-21/A1 2009

Classifications

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.