K8DS-PA1 387485 K8DS0006C OMRON Monitoring Relays, Three Phase Asymmetry Sequence + Lost + 17.5mm phase 200-.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

K8DS-PA1 387485 K8DS0006C OMRON Monitoring Relays, Three Phase Asymmetry Sequence + Lost + 17.5mm phase 200-..

K8DS-PA1

387485

K8DS0006C

OMRON

Available

Ship on today

Monitoring Relays, Three Phase Asymmetry Sequence + Lost + 17.5mm phase 200-240AC

More details


K8DS

* Brand new product in its original packaging covered by the warranties and certifications provided by OMRON

*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Ordering information

Rated input

Order code

3-phase 3-wire mode

200, 220, 230, 240 VAC

K8DS-PA1

3-phase 3-wire mode

380, 400, 415, 480 VAC

K8DS-PA2

Specifications

Ambient operating temperature

-20 to 60°C (with no condensation or icing)

Storage temperature

-25 to 65°C (with no condensation or icing)

Altitude

2,000 m max.

Input frequency

50/60 Hz (AC power supply)

Output relays
(1 × SPDT, normally closed operation)

Resistive load

5 A at 250 VAC or at 30 VDC

Maximum contact voltage

250 VAC or 30 VDC

Maximum contact current

5 A

Maximum switching capacity

1,250 VA, 150 W

Mechanical life

10,000,000 operations

Electrical life

50,000 operations at 5 A, 250 VAC or 30 VDC

Degree of protection

Terminal section: IP20

Case material

PC UL94 V-0

Weight

Approx. 65 g

Rated input voltage

K8DS-PA1

3-phase, 3-wire mode: 200, 220, 230, 240 VAC

K8DS-PA2

3-phase, 3-wire mode: 380, 400, 415, 480 VAC

Asymmetry operation (ASY.)

Operating value setting range

Asymmetry rate: 2% to 22%

Operating value

100% operation at set value

Asymmetry operating value = rated input voltage x asymmetry set value [%]

The asymmetry operation will function when the difference between the highest and lowest voltage phases equals or exceeds the asymmetry operating value

Reset (HYS.)

Hysteresis

5% of operating value (fixed)

Resetting method

Automatic reset

Operating time (T)

Asymmetry

0.1 to 30 s

Phase-sequence

0.1 s ±0.5 s

Phase-loss

0.1 s max.

Power ON lock (LOCK)

1 s ±0.5 s

Overload capacity

Continuous input: 500 V

Repeat accuracy

Operating value

±0.5% full scale (at 25°C and an ambient humidity of 65% at the rated power supply voltage, 50/60 Hz sine wave input)

Operating time

±50 ms (at 25°C and 65% humidity, rated power supply voltage)

Indicators

Power (PWR): Green, Relay output (RY): Yellow, Alarm outputs (ALM): Red

Applicable standards

Conforming standards

EN 60947-5-1
Installation environment (pollution level 2, installation category III)

EMC

EN 60947-5-1

Safety standards

UL 508 (Recognition), Korean Radio Waves Act (Act 10564), CSA: C22.2 No. 14, CCC: GB14048.5

Size (H × W × D)

80 × 17.5 × 74 mm

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.