E5C2-R40K AC100-240 0-600 378348 E5C26016G OMRON Temperature and Process Proportional 0-600ºC 48x48 K Thermo.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

E5C2-R40K AC100-240 0-600 378348 E5C26016G OMRON Temperature and Process Proportional 0-600ºC 48x48 K Thermo..

E5C2-R40K AC100-240 0-600

378348

E5C26016G

OMRON

Available

Ship on today

Temperature and Process Proportional 0-600ºC 48x48 K Thermocouple

More details


E5C2

* Brand new product in its original packaging covered by the warranties and certifications provided by OMRON

*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Ordering information

Standard models (Power supply: 100 to 240 VAC)

Input

Control method

On/OFF

Proportional (P)

Output/Indication method

Relay/No indication

Input/ standard scale (°C)

Thermocouple

K (CA) Chromel vs. Alumel

0 to 200 °C

E5C2-R20K AC100-240 0-200

E5C2-R40K AC100-240 0-200

0 to 300 °C

-

E5C2-R40K AC100-240 0-300

0 to 400 °C

E5C2-R20K AC100-240 0-400

E5C2-R40K AC100-240 0-400

0 to 600 °C

E5C2-R20K AC100-240 0-600

E5C2-R40K AC100-240 0-600

0 to 800 °C

E5C2-R20K AC100-240 0-800

E5C2-R40K AC100-240 0-800

0 to 1000 °C

E5C2-R20K AC100-240 0-1000

-

0 to 1200 °C

E5C2-R20K AC100-240 0-1200

-

J (IC) Iron versus Constantan

0 to 200 °C

E5C2-R20J AC100-240 0-200

-

0 to 300 °C

E5C2-R20J AC100-240 0-300

-

0 to 400 °C

E5C2-R20J AC100-240 0-400

-

Resistance thermometer

Platinum resistance thermometer

-50 to 50 °C

E5C2-R20P-D AC100-240 -50-50

-

0 to 50 °C

E5C2-R20P-D AC100-240 0-50

-

0 to 100 °C

E5C2-R20P-D AC100-240 0-100

-

0 to 200 °C

E5C2-R20P-D AC100-240 0-200

-

0 to 300 °C

E5C2-R20P-D AC100-240 0-300

-

0 to 400 °C

E5C2-R20P-D AC100-240 0-400

-

Thermistor

THE (replaceable element)

0 to 100 °C

E5C2-R20G AC100-240 0-100

-

100 to 200 °C

E5C2-R20G AC100-240 100-200

-

150 to 300 °C

E5C2-R20G AC100-240 150-300

-

 

Input ranges

Thermocouple

Platinum resistance thermometer

Thermistor

K (CA) chromel vs. alumel

J (IC) iron vs. constantan

Pt100

THE

°C

0 to 200 (5),
0 to 400 (10),
0 to 600 (20),
0 to 800 (20),
0 to 1,000 (25),
0 to 1,200 (25)

0 to 200 (5),
0 to 300 (10),
0 to 400 (10)

-50 to 50 (2),
0 to 50 (1),
0 to 100 (2),
0 to 200 (5),
0 to 300 (10),
0 to 400 (10)

0 to 100 (2) (6 kΩ at 0°C),
100 to 200 (2) (550 Ω ☐ 200°C)

150 to 300 (2) (4 kΩ ☐ 200°C)

Accessories

Functions

Order code

Front connecting socket with finger protection

P2CF-08-E

Back connecting socket (for flush mounting)

P3G-08

Finger protection cover (for P3G-08)

Y92A-48G

Protective front cover (IP66)

Y92A-48B

Specifications

Supply voltage

100 to 240 VAC, 50/60 Hz

Thermocouple input type

K, J (with sensor break detection)

RTD input type

Pt100, THE

Control mode

ON/OFF or P control

Setting method

analog setting

Output

Relay, SPDT, 3 A at 250 VAC

Life expectancy

Electrical: 100,000 operations min.

Setting accuracy

±2% FS max.

Hysteresis

Approx. 0.5% FS (fixed)

Proportional band

3% FS (fixed)

Reset range

5 ±1% FS min.

Control period

20 s

IP Rating front panel

IP40 (IP66 cover available)

IP rating terminals

IP00

Ambient temperature

-10 to 55°C

Size in mm (HxWxD)

48×48×96

 


1.Values in ( ) are the minimum unit.

2.Values in ( ) are the thermistor resistive value.

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Últimas Opiniones de Nuestros Clientes

Todas las valoraciones que recibimos de los artículos que ofrecemos son reales y están verificadas. Un pequeño gesto, pero de mucho valor. Por eso, te agradecemos ese minuto que inviertes en dejarnos tu opinión y calificación sobre los productos, porque nos ayuda a seguir mejorando y a ofrecerte un servicio de todavía mayor calidad.