Generator connection box, type 2, with four fuse holders for 4 x 1 string. System solution for photovoltaic fuses for photovoltaic inverters with 1 MPP tracker• Error-resistant Y circuit to VDE 0100-712 (50539-12) • Low DC protection level: < 4.0 kV (Voc max = 1,000 V DC with V20-C/0-500PV) • Item no.: 5088654: (+) poles protected via 4 photovoltaic fuses 10 x 38 mm (unequipped), 1,000 V DC protected• Item no.: 5088640: (+) poles protected via 4 photovoltaic fuses 10 x 38 mm (unequipped), 900 V DC protected• 4 (-) poles via terminal up 6 mm² switched in parallel in the housing, up to 30 A DC per terminal• Pre-mounted in polycarbonate housing (IP65), UV-resistant for use outside, including cable gland kitFor DC protection of the inverter in photovoltaic systems.If there is a danger of con

More details


TBS Transient and lightning protection systems - OBO BETTERMANN

Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Anschlussart GeneratoranschlusskastenTension spring terminal
CO2 Footprint (GWP) Cradle-to-Gate2,3932 kg CO2e / 1 Piece
ColourLight grey; RAL 7035
Conductor cross-section, rigid (single-wire/multiwire), max.6 mm²
Conductor cross-section, rigid (single-wire/multiwire), min.0,5 mm²
DC network formyes
Depth122 mm
Dimension1000V DC
Entries per MPPT4
Entry fuse10 A
Equipped with load-break switchno
Exits per MPPT4
For fuse size10x38 mm
Fuse typegPV (full-range photovoltaic protection) [Bitte prüfen, ob so in Ordnung]
Installation typePre-mounted in the housing
IT network formno
Lightning protection zone LPZ1→2
Max. Input current per string30 A
Max. Input voltage DC1000 V
Max. Output current30 A
Maximum continuous voltage DC1000 V
Maximum discharge current (8/20 μs)40 kA
Monitoring functionno
Network formDC
Nominal discharge current (8/20 µs)20 kA
Number of cable entries16
Number of inputs4
Number of MPPTs1
Number of string inputs4
Operating temperature, max.80 °C
Operating temperature, min.-40 °C
Other network formno
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Protection ratingIP65
Remote signallingno
Response time<25 ns
Signalling on deviceVisual
SPD to EN 61643-11Type 2
SPD to IEC 61643-1Class II
String fuse1-pole
TN network formno
TN-C network formno
TN-C-S network formno
TN-S network formno
TT network formno
Type of entryGland
Version forType 2 in housing with fuse holder (unequipped)

Datasheet - PDF

Title: Size: Type:
PDF CATALOGUE SURGE PROTECTION OBO EN.pdf 24 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.