TKS-B 5097976 OBO BETTERMANN Lightning barrier , 120V AC,

Reference: TKS-B

Code: 5097976

Manufacturer: OBO BETTERMANN

Description:

Lightning barrier , 120V AC,
Basic protection for two-core systems with HF applications 120 V. TKS-B: Surge protection for use in measuring, control and regulation systems, as well as telecommunication systems • Basic protection for lightning protection equipotential bonding• High impulse arresting capacity 6 kA (10/350) • With installation-friendly, screwless connection terminals • In space-saving 17.5 mm grid Application: Universal use on 35 mm DIN profile rail in any standard distributor housing.

Categories:

  • Earthing, lightning and surge protection > Combined arrester for data networks/MCR-technology
  • OBO BETTERMANN > TBS Transient and lightning protection systems - OBO BETTERMANN > Surge protection, arrestor, type 3 - OBO BETTERMANN

Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 82,70 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

Capacity (wire-earth)<10 pF
Capacity (wire-wire)<10 pF
CO2 Footprint (GWP) Cradle-to-Gate0,2006 kg CO2e / 1 Piece
Connection cross-section, flexible, max.2,5 mm²
Connection cross-section, flexible, min.0,14 mm²
Connection cross-section, multi-wire, max.2,5 mm²
Connection cross-section, multi-wire, min.0,14 mm²
Connection cross-section, rigid, max.2,5 mm²
Connection cross-section, rigid, min.0,14 mm²
Cut-off frequency250 MHz
Dimension120V AC
Division unit TE (17.5 mm)1
Earthing via:Connection cable
Impulse durability wire-earthC2: 18 kV / 9 kA
Impulse durability wire-wireC2: 18 kV / 9 kA
Insertion loss3 dB @ 250 MHz dB
Insulation resistance>1 GΩ
KategorieType 1+2 / D1+C2
Lightning protection zone LPZ0→2
Maximum continuous voltage AC120 V
Maximum continuous voltage DC170 V
Nominal load current AC14 A
Nominal load current DC20 A
Number of poles2
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Plug-in systemTerminal
Protection level wire-earth<600 V
Protection level wire-wire<950 V
Protection ratingIP20
Shielding connection availableno
SPD to IEC 61643-21Class I+II / D1+C2
Testing standardIEC 61643-21
Total discharge current (10/350)D1: 6 kA
Total discharge current (8/20)18 kA

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.