ANUNCIAR
TD-2/D-HS 5081694 OBO BETTERMANN Surge protection device for TK systems with hat rail, White, Plastic View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

TD-2/D-HS 5081694 OBO BETTERMANN Surge protection device for TK systems with hat rail, White, Plastic

TD-2/D-HS

5081694

OBO BETTERMANN

Surge protection device for TK systems with hat rail, White, Plastic

Combination protection device for ISDN and DSL systems. Data cable protection devices for telecommunication systems • Low protection level at high current load • Screwless terminals or connectable • Bandwidth-optimised for secure transmission • Quick mounting onto DIN rail for a telephone line • Visual function display Application: DSL systems, ISDN or analogue telecommunication

More details


Earthing, lightning and surge protection > Surge protection device for data networks/MCR-technology

TBS Transient and lightning protection systems - OBO BETTERMANN > Surge protection, arrestor, type 3 - OBO BETTERMANN

Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN

Total: $132.75
Unit price: $132.75
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Arrestor monitoringno
Capacity (wire-earth)<50 pF
Capacity (wire-wire)<50 pF
CO2 Footprint (GWP) Cradle-to-Gate0,2096 kg CO2e / 1 Piece
ColourWhite
Connection cross-section, flexible, max.2,5 mm²
Connection cross-section, flexible, min.0,14 mm²
Connection cross-section, multi-wire, max.2,5 mm²
Connection cross-section, multi-wire, min.0,14 mm²
Connection cross-section, rigid, max.2,5 mm²
Connection cross-section, rigid, min.0,14 mm²
Cut-off frequency75 MHz
Dimension170V
Division unit TE (17.5 mm)1
Earthing via:Connection cable
Explosion-tested versionno
Impulse durability wire-earthC2: 18 kV / 9 kA (8/20µs)
Impulse durability wire-wireC2: 18 kV / 9 kA (8/20µs)
Insertion loss≤3 dB
Insulation resistance>1 MΩ
KategorieType 1+2+3 / D1+C2+C1
Lightning impulse current2,5 kA
Lightning protection zone LPZ0→3
MaterialPlastic
Maximum continuous voltage AC120 V
Maximum continuous voltage DC170 V
Nominal load current AC0,14 A
Nominal load current DC0,2 A
Number of poles2
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Plug-in systemTerminal
Protection level wire-earth<650 V
Protection level wire-wire<300 V
Protection ratingIP20
ScreeningDirect
Series resistance per wire9 Ω ± 10 %
Shielding connection availableno
Signalling on deviceVisual
SPD to IEC 61643-21Class I+II+III / D1+C2+C1
Telecommunications contactno
Testing standardIEC 61643-21
Total discharge current (10/350)D1: 5 kA
Total discharge current (8/20)10 kA

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.