ANUNCIAR
FRD 5 5098492 OBO BETTERMANN Lightning barrier with decoupling resistance, 5V AC, View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

FRD 5 5098492 OBO BETTERMANN Lightning barrier with decoupling resistance, 5V AC,

FRD 5

5098492

OBO BETTERMANN

Lightning barrier with decoupling resistance, 5V AC,

Medium and fine protection FRD for two-core systems 5 V. Surge protection for use in measurement and control technology • Medium and fine protection • Standard design for double core systems • Two-stage protection circuit • With installation-friendly, screwless connection terminals • In space-saving 17.5 mm grid • With ohmic decoupling in the longitudinal branchApplication: Universal use on any 35 mm DIN profile rail in every commercially available distributor housing.

More details


Earthing, lightning and surge protection > Combined arrester for data networks/MCR-technology

TBS Transient and lightning protection systems - OBO BETTERMANN > Surge protection, arrestor, type 3 - OBO BETTERMANN

Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN

Total: $120.30
Unit price: $120.30
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



ApprovalsUL
Arrestor monitoringno
Capacity (wire-earth)<1 nF
Capacity (wire-wire)<10 nF
CO2 Footprint (GWP) Cradle-to-Gate0,2968 kg CO2e / 1 Piece
Connection cross-section, flexible, max.2,5 mm²
Connection cross-section, flexible, min.0,14 mm²
Connection cross-section, multi-wire, max.2,5 mm²
Connection cross-section, multi-wire, min.0,14 mm²
Connection cross-section, rigid, max.2,5 mm²
Connection cross-section, rigid, min.0,14 mm²
Cut-off frequency0,63 MHz
Dimension5V AC
Division unit TE (17.5 mm)1
Earthing via:Terminal
Explosion-tested versionno
Impulse durability wire-earthC2: 10 kV / 5 kA (8/20µs)
Impulse durability wire-wireC1: 1 kV / 0,5 kA (8/20µs)
Insertion loss3 dB @ 630 kHz dB
Insulation resistance>1 MΩ
KategorieType 1+2+3 / D1+C2+C1
Lightning impulse current1,5 kA
Lightning protection zone LPZ0→3
Maximum continuous voltage AC5 V
Maximum continuous voltage DC8 V
Nominal discharge current (8/20 µs)5 kA
Nominal load current AC0,14 A
Nominal load current DC0,2 A
Nominal voltage5 V
Number of poles2
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Plug-in systemTerminal
Protection level wire-earth<600 V
Protection level wire-wire<15 V
Protection ratingIP20
Series resistance per wire15 Ω ± 10 %
Shielding connection availableno
SPD to IEC 61643-21Class I+II+III / D1+C2+C1
Telecommunications contactno
Testing standardIEC 61643-21
Total discharge current (10/350)D1: 3 kA
Total discharge current (8/20)10 kA

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.