ANUNCIAR
MCD 50-B-OS 5096852 OBO BETTERMANN Coordinated lightning cont. with function display, 255V, View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MCD 50-B-OS 5096852 OBO BETTERMANN Coordinated lightning cont. with function display, 255V,

MCD 50-B-OS

5096852

OBO BETTERMANN

Coordinated lightning cont. with function display, 255V,

Combination arrester, 1-pole with function display. Combination arrester, type 1+2, 1-pole, for use in TN and TT networks:MCD 50-B-OS: Coordinated lightning current arrester, type 1+2 to EN 61643-11 with visual function display. For interface 0 to 2 (LPZ) in accordance with lightning protection zone concept to IEC 62305 and/or DIN VDE 0185-305.• Arresting capacity 50 kA (10/350 µs) per pole • Power consumption < 26 mW/pole• Protection level < 1.7 kV, allows device protection• Line follow current quenching 10 kA • lncl. plug caps for labelling the connections• Encapsulated, non-extinguishing spark gap• Can be used in standard distributor housings Application: Compact surge protection concepts and installations in a distributor.

More details


Earthing, lightning and surge protection > Lightning current arrester for power supply systems

TBS Transient and lightning protection systems - OBO BETTERMANN > Surge protection, arrestor, type 1 (industry) - OBO BETTERMANN

Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN

Total: $285.84
Unit price: $285.84
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Often bought together

Best sellers

More info



ApprovalsVDE
Arrester surge current (8/20 µs) [total]50 kA
Blow-outno
CO2 Footprint (GWP) Cradle-to-Gate2,0355 kg CO2e / 1 Piece
Conductor cross-section, rigid (single-wire/multiwire), max.50 mm²
Conductor cross-section, rigid (single-wire/multiwire), min.10 mm²
DC network formno
Dimension255V
Height69 mm
Installation typeDIN rail 35 mm
IT network formno
Length100 mm
Lightning protection zone LPZ0→2
Lightning surge current (10/350 μs)50 kA
Lightning surge current (10/350)50 kA
Max. mains-side overcurrent protection500
Maximum back-up fuse500 A
Maximum continuous voltage (L-N)255 V
Maximum continuous voltage AC255 V
Network formTN-S, TT
Nominal discharge current (8/20 µs)50 kA
Nominal discharge current (8/20 µs) [L-N]50 kA
Nominal voltage AC (50/60 Hz)230 V
OBO_Nominal load current (input/output terminal)125 A
Operating temperature, max.85 °C
Operating temperature, min.-40 °C
Other network formno
Permitted temperature range, max.85 °C
Permitted temperature range, min.-40 °C
Pole number1
Pole version1
Protection level [L-N]≤1,7
Protection ratingIP20
Remote signallingno
Response time<100 ns
Short-circuit resistance10 kA
Short-circuit resistance for max. mains-side overcurrent protection10 kA
Signalling on deviceVisual
SPD to EN 61643-11Type 1+2
SPD to IEC 61643-1Class I+II
Test class, type 1yes
Test class, type 2yes
TN network formyes
TN-C network formyes
TN-C-S network formyes
TN-S network formyes
TT network formyes
Version for1-pole
Width35 mm

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.