OBO BETTERMANN MCF75-3+FS 5096981 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

MCF75-3+FS 5096981 OBO BETTERMANN UNLOADER COMB. BEAM COMPACT

Reference: MCF75-3+FS

Code: 5096981

Manufacturer: OBO BETTERMANN

Description:

UNLOADER COMB. BEAM COMPACT
LightningController Compact - MCF75. Combination arrester, lightning current and surge arrester, type 1+2• Protection level ≤ 1.5 kV• For lightning protection equipotential bonding to VDE 0185-305 (IEC 62305)• Lightning current arresting capacity to 75 kA (10/350), 3-pole• Line following current quenching 50 kA Ipeak, arrester backup fuse to 315 A gL/gG• Fulfils the requirements of VDE-AR-N 4100 for use in pre-meter area• Encapsulated, non-extinguishing spark gap arrester for use in distributor housings Application: Industrial systems and buildings with external lightning protection of the highest class I to IV.Compact protection device

Categories:

  • OBO BETTERMANN > TBS Transient and lightning protection systems - OBO BETTERMANN

Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN

  • More Info
  • Reviews
Guarantee, repair and return.

Unit Price: 472,30 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

MORE INFO

ApprovalsVDE, UL
Arrester surge current (8/20 µs) [total]75 kA
CO2 Footprint (GWP) Cradle-to-Gate3,7009 kg CO2e / 1 Piece
Conductor cross-section, flexible (fine-wire), max.3 AWG
Conductor cross-section, flexible (fine-wire), max.25 mm²
Conductor cross-section, flexible (fine-wire), min.1,5 mm²
Conductor cross-section, flexible (fine-wire), min.16 AWG
Conductor cross-section, rigid (single-wire/multiwire), max.35 mm²
Conductor cross-section, rigid (single-wire/multiwire), max.2 AWG
Conductor cross-section, rigid (single-wire/multiwire), min.16 AWG
Conductor cross-section, rigid (single-wire/multiwire), min.1,5 mm²
Connection cross-section, FM terminals, max.16 AWG
Connection cross-section, FM terminals, max.1,5 mm²
Connection cross-section, FM terminals, min.28 AWG
Connection cross-section, FM terminals, min.0,5 mm²
Dimension255V
FM contactsChangeover
Height70 mm
Housing material surge protection componentsPA UL 94 V-0
Installation typeDIN rail 35 mm
Length90 mm
Lightning surge current (10/350 μs)25 kA
Lightning surge current (10/350)75 kA
Max. mains-side overcurrent protection315 A
Maximum back-up fuse315 A
Maximum continuous voltage AC255 V
Maximum discharge current (8/20 μs)50 kA
Network formTN-C
Nominal discharge current (8/20 µs)35 kA
Nominal voltage AC (50/60 Hz)230 V
Operating temperature, max.80 °C
Operating temperature, min.-40 °C
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Pole number3
Pole version3
Protection ratingIP20
Remote signallingyes
Response time<100 ns
Short-circuit resistance for max. mains-side overcurrent protection50 kA eff
Signalling on deviceVisual
SPD to EN 61643-11Type 1+2
SPD to IEC 61643-1Class I+II
SPD to UL 1449Type 4
Switching power AC250V/ 1,5A
Switching power DC250V/ 0,1A
TN network formyes
TN-C network formyes
Torque5 Nm
TOV voltage [L-N] ‒ fail safe mode ‒ 120 min.442 V
TOV voltage [L-N] ‒ withstand mode ‒ 5 s440 V
Width107 mm

DATASHEET - PDF

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.