FLD 2-110 5098859 OBO BETTERMANN ARRESTER SURGE FLD 2-110

FLD 2-110

5098859

OBO BETTERMANN

ARRESTER SURGE FLD 2-110

Medium and fine protection FLD 2 for two-core systems 110 V. Surge protection for use in measurement and control technology • Medium and fine protection • Standard design for single core systems • Two-stage protection circuit • With installation-friendly, screwless connection terminals • In space-saving 17.5 mm grid • With inductive decoupling in the longitudinal branchApplication: Universal use on any 35 mm DIN profile rail in every commercially available distributor housing.

More details


TBS Transient and lightning protection systems - OBO BETTERMANN

Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



ApprovalsUL
Capacity (wire-earth)<10 nF
Capacity (wire-wire)< 1 nF
CO2 Footprint (GWP) Cradle-to-Gate0,1438 kg CO2e / 1 Piece
Connection cross-section, flexible, max.2,5 mm²
Connection cross-section, flexible, min.0,14 mm²
Connection cross-section, multi-wire, max.2,5 mm²
Connection cross-section, multi-wire, min.0,14 mm²
Connection cross-section, rigid, max.2,5 mm²
Connection cross-section, rigid, min.0,14 mm²
Dimension110V AC
Division unit TE (17.5 mm)1
Earthing via:Terminal
Explosion-tested versionno
Impulse durability wire-earthC2: 5 kV / 2,5 kA (8/20µs)
Impulse durability wire-wireC2: 5 kV / 2,5 kA (8/20µs)
Insertion loss3dB @ 150 kHz dB
Insulation resistance>1MΩ
KategorieType 2+3 / C2+C1
Lightning protection zone LPZ1→3
Maximum continuous voltage AC86 V
Maximum continuous voltage DC122 V
Nominal discharge current (8/20 µs)0,5 kA
Nominal load current AC0,7 A
Nominal load current DC1 A
Number of poles2
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Plug-in systemTerminal
Protection level wire-earth<300 V
Protection level wire-wire<500 V
Protection ratingIP20
Series inductivity per wire120 µH ± 10 %
Shielding connection availableno
SPD to IEC 61643-21Class II+III / C2+C1
Telecommunications contactno
Testing standardIEC 61643-21
Total discharge current (8/20)5 kA

Datasheet - PDF

Title: Size: Type:
PDF CATALOGUE SURGE PROTECTION OBO EN.pdf 24 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.