5093510 OBO BETTERMANN ARRESTER 1+2 V50-0-385 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

5093510 OBO BETTERMANN ARRESTER 1+2 V50-0-385

V50-0-385

5093510

OBO BETTERMANN

ARRESTER 1+2 V50-0-385

Plug-in arrester V50 385 V. Combination arrester, type 1+2 • For lightning protection equipotential bonding to VDE 0185-305 (IEC 62305) • Lightning current discharge capacity of 12.5 kA (10/350) per pole • Modular, plug-in arrester with dynamic cut-off unit and visual status display • Locking mechanism with vibration protection and voltage keying • Plastic (UL 94 V-0)

More details


Earthing, lightning and surge protection > Combined arrester for power supply systems

TBS Transient and lightning protection systems - OBO BETTERMANN

Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Blow-outno
CO2 Footprint (GWP) Cradle-to-Gate0,8612 kg CO2e / 1 Piece
Conductor cross-section, flexible (fine-wire), max.2 AWG
Conductor cross-section, flexible (fine-wire), max.35 mm²
Conductor cross-section, flexible (fine-wire), min.16 AWG
Conductor cross-section, flexible (fine-wire), min.1,5 mm²
Conductor cross-section, rigid (single-wire/multiwire), max.35 mm²
Conductor cross-section, rigid (single-wire/multiwire), max.2 AWG
Conductor cross-section, rigid (single-wire/multiwire), min.1,5 mm²
Conductor cross-section, rigid (single-wire/multiwire), min.16 AWG
Connection cross-section, FM terminals, max.1,5 mm²
Connection cross-section, FM terminals, max.16 AWG
Connection cross-section, FM terminals, min.0,5 mm²
Connection cross-section, FM terminals, min.21 AWG
Dimension385V
Housing material surge protection componentsPA UL 94 V-0
Installation typeDIN rail 35 mm
Integrated back-up fuseno
Lightning surge current (10/350 μs)12,5 kA
Max. mains-side overcurrent protection160 A gL/gG
Maximum back-up fuse160 A
Maximum continuous voltage (L-N)385 V
Maximum continuous voltage AC385 V
Maximum discharge current (8/20 μs)50 kA
Maximum discharge current (8/20 μs) [L-N]50 kA
Minimum distance1,5 mm
Network formAll
Nominal discharge current (8/20 µs)30 kA
Nominal discharge current (8/20 µs) [L-N]30 kA
Nominal voltage AC (50/60 Hz)350 V
Operating temperature, max.80 °C
Operating temperature, min.-40 °C
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Pole number1
Pole version1
Protection level [L-N]≤1,7
Protection ratingIP20
Remote signallingno
Residual voltage [L-N] @ 1 kA1,1 kV
Residual voltage [L-N] @ 12.5 kA1,3 kV
Residual voltage [L-N] @ 5 kA1,2 kV
Response time<25 ns
Short-circuit resistance for max. mains-side overcurrent protection50 kA eff
Signalling on deviceVisual
SPD to EN 61643-11Type 1+2
SPD to IEC 61643-1Class I+II
SPD to UL 1449Type 4
Torque4 Nm
TOV voltage [L-N] ‒ fail safe mode ‒ 120 min.670 V
TOV voltage [L-N] ‒ withstand mode ‒ 5 s510 V

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.