5081990 OBO BETTERMANN DATA PROTECTION RJ45 S-ATM8-IND

Reference: RJ45 S-ATM 8-F

Code: 5081990

Manufacturer: OBO BETTERMANN

Description:

DATA PROTECTION RJ45 S-ATM8-IND
Fine protection 8-F for Ethernet networks (Class D/CAT 5). Universal data cable protection device for network technology and telecommunication systems • In aluminium housing • Protection for 8 cores • With two-stage protective circuit • Simple mounting• With RJ45 Western connector• Incl. 150 mm connection cable with RJ45 connectors• Cat 5e network technology, 10BaseT, 100BaseT, 1000BaseT• DIN rail mounting with accessories DLS-BS (5082 38 2)Application: For analogue, ISDN, DSL systems, Ethernet Twisted Pair.• Usable in networks of Class D or CAT 5e• Can be locked onto DIN profile rails or mounted directly at the terminal• Simple installation using RJ45 connection technology• Optimised transmission properties

Categories:

  • Earthing, lightning and surge protection > Surge protection device for data networks/MCR-technology
  • OBO BETTERMANN > TBS Transient and lightning protection systems - OBO BETTERMANN

Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 88,13 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

MORE INFO

Arrestor monitoringno
Capacity (wire-earth)<10 pF
Capacity (wire-wire)<50 pF
Channel performance Ansi/EACAT 5e
Channel performance ISO/IECClass D
CO2 Footprint (GWP) Cradle-to-Gate1,5752 kg CO2e / 1 Piece
Cut-off frequency155 MHz
Dimension6.2V
Earthing via:Connection cable
Impulse durability wire-earthC2: 3 kV / 1,5 kA (8/20µs)
Impulse durability wire-wireC2: 3 kV / 1,5 kA (8/20µs)
Insertion loss<3 @ 150 MHz dB
Insulation resistance>1 GΩ
KategorieType 2+3 / C2+C1
Lightning protection zone LPZ1→3
Maximum continuous voltage AC4,2 V
Maximum continuous voltage DC6 V
Number of poles8
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Plug-in systemRJ45 8(8)
Protection level wire-earth<900 V
Protection level wire-wire<40 V
Protection ratingIP40
ScreeningDirect
Shielding connection availableyes
SPD to IEC 61643-21Class II+III / C2+C1
Testing standardIEC 61643-21
Total discharge current (8/20)7,5 kA
Version forFine protection, 8 wires + shield

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.