PHOENIX CONTACT  STTBS 4-TG 3035483 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

STTBS 4-TG 3035483 PHOENIX CONTACT Disconnect terminal block

Reference: STTBS 4-TG

Code: 3035483

Manufacturer: PHOENIX CONTACT

Description:

Disconnect terminal block
Interruptible terminal, Current and voltage are determined by the connector used., nominal voltage: 500 V, nominal current: 28 A, connection type: Spring connection, Dimensioning cross-section: 2.5 mm², cross-section: 0.08 mm² - 6 mm², cross-section: 0.08 mm² - 6 mm², mounting class: NS 35/7.5, NS 35/15, colour: grey
Disconnect terminal block, Current and voltage are determined by the plug used., nom. voltage: 500 V, Thermal continuous current Ith: 28 A, connection method: Spring-cage connection, Rated cross section: 4 mm2, cross section: 0.08 mm2 - 6 mm2, cross section: 0.08 mm2 - 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: gray

Categories:

  • Terminal blocks > Feed-through terminal block
  • PHOENIX CONTACT > Modular TBs

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • ETIM
  • PDF
  • Reviews
Guarantee, repair and return.

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

LAST VIEWED

MORE INFO

Technical data

Notes
GeneralCurrent and voltage are determined by the plug used.
General
NoteCurrent and voltage are determined by the component used.

Product properties
Product typeDisconnect terminal block
Number of connections4
Number of rows2
Potentials2
Data management status
Article revision01
Insulation characteristics
Overvoltage categoryIII

Electrical properties
Rated surge voltage6 kV
Maximum power dissipation for nominal condition1.02 W

Connection data
Number of connections per level2
Nominal cross section4 mm²
Level 1
Stripping length8 mm ... 10 mm
Internal cylindrical gageA4
Connection in acc. with standardIEC 60947-7-1
Conductor cross section rigid0.08 mm² ... 6 mm²
Cross section AWG28 ... 10 (converted acc. to IEC)
Conductor cross section flexible0.08 mm² ... 4 mm²
Conductor cross section, flexible [AWG]28 ... 12 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)0.14 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.14 mm² ... 4 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve0.5 mm² ... 1 mm²
Thermal continuous current Ith28 A (with 4 mm² conductor cross-section)
Maximum load current34 A (with 6 mm² conductor connection)
Nominal voltage500 V
Nominal cross section4 mm²
Level 2
Stripping length8 mm ... 10 mm
Connection in acc. with standardIEC 60947-7-1
Conductor cross section rigid0.08 mm² ... 6 mm²
Cross section AWG28 ... 10 (converted acc. to IEC)
Conductor cross section flexible0.08 mm² ... 4 mm²
Conductor cross section, flexible [AWG]28 ... 12 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)0.14 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.14 mm² ... 4 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve0.5 mm² ... 1 mm²
Thermal continuous current Ith20 A (with a 2.5 mm² conductor cross section)
Maximum load current20 A (with a 2.5 mm² conductor cross section)
Nominal voltage500 V

Dimensions
Width6.2 mm
End cover width2.2 mm
Height92.4 mm
Depth on NS 35/7,555 mm
Depth on NS 35/1562.5 mm

Material specifications
Colorgray (RAL 7042)
Flammability rating according to UL 94V0
Insulating material groupI
Insulating materialPA
Static insulating material application in cold-60 °C
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed

Electrical tests
Surge voltage test
Test voltage setpoint7.3 kV
ResultTest passed
Temperature-rise test
Requirement temperature-rise testIncrease in temperature ≤ 45 K
ResultTest passed
Short-time withstand current 4 mm²0.48 kA
Short-time withstand current 2.5 mm²0.3 kA
ResultTest passed
Power-frequency withstand voltage
Test voltage setpoint1.89 kV
ResultTest passed

Mechanical properties
Mechanical data
Open side panelYes

Mechanical tests
Attachment on the carrier
DIN rail/fixing supportNS 32/NS 35
Test force setpoint1 N
ResultTest passed
Test for conductor damage and slackening
Rotation speed9 rpm
Revolutions135
Conductor cross section/weight0.08 mm² / 0.1 kg
4 mm² / 0.9 kg
6 mm² / 1.4 kg
ResultTest passed

Environmental and real-life conditions
Aging
Temperature cycles192
ResultTest passed
Needle-flame test
Time of exposure30 s
ResultTest passed
Oscillation/broadband noise
SpecificationDIN EN 50155 (VDE 0115-200):2022-06
SpectrumService life test category 2, bogie-mounted
Frequencyf1= 5 Hz to f2= 250 Hz
ASD level6.12 (m/s²)²/Hz
Acceleration3.12g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
ResultTest passed
Shocks
Pulse shapeHalf-sine
Acceleration5g
Shock duration30 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
ResultTest passed
Ambient conditions
Ambient temperature (operation)-60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)-5 °C ... 70 °C
Ambient temperature (actuation)-5 °C ... 70 °C
Permissible humidity (operation)20 % ... 90 %
Permissible humidity (storage/transport)30 % ... 70 %

Standards and regulations
Connection in acc. with standardIEC 60947-7-1
IEC 60947-7-1

Mounting
Mounting typeNS 35/7,5
NS 35/15

ETIM for 3035483 Terminal blocks (EC000902)

Feature nameConnectable conductor cross section fine-strand without cable end sleeve (EF007341)
Feature value0.08 mm²
Feature nameConnectable conductor cross section fine-strand with cable end sleeve (EF007339)
Feature value0.14 mm²
Feature nameConnectable conductor cross section solid-core (EF007337)
Feature value0.08 mm²
Feature nameRated voltage (EF000228)
Feature value500 V
Feature nameType of electrical connection 1 (EF002526)
Feature valueSpring clamp connection
Feature nameType of electrical connection 2 (EF002527)
Feature valueSpring clamp connection
Feature nameNumber of clamp positions per level (EF002660)
Feature value2
Feature nameInternally connected stages (EF002661)
Feature valueYes
Feature nameMounting method (EF000003)
Feature valueDIN rail (top hat rail) 35 mm
Feature nameMaterial insulation body (EF007543)
Feature valueOther
Feature nameInflammability class of insulation material according to UL94 (EF002521)
Feature valueV0
Feature nameWidth (EF000008)
Feature value6.2 mm
Feature nameHeight (EF000040)
Feature value92.4 mm
Feature nameDepth (EF000049)
Feature value55 mm
Feature nameClosing plate required (EF002525)
Feature valueYes
Feature nameColour (EF000007)
Feature valueGrey
Feature nameType of cross disconnection (EF002546)
Feature valueNone
Feature nameWith integrated test socket (EF002547)
Feature valueNo

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.