EATON - MOELLER PLS6-C20/2-DC-MW 243136 Y7-243136 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

PLS6-C20/2-DC-MW 243136 Y7-243136 EATON ELECTRIC Over current switch, 20A, 2p, type C characteristic, DC

Reference: PLS6-C20/2-DC-MW

Code: 243136

Catalog Number: Y7-243136

Manufacturer: EATON - MOELLER

Description:

Over current switch, 20A, 2p, type C characteristic, DC
PLS6-C20/2-DC-MW
Eaton Moeller series xPole - PLS6-DC MCB. PLS6, 2-pole, tripping characteristic: C, rated current In: 20 A, rated switching capacity acc. to IEC/EN 60947-2: 6 kA, Switchgear for DC applications
Miniature circuit breaker (MCB), PLS6, 2-pole, tripping characteristic: C, rated current In: 20 A, rated switching capacity acc. to IEC/EN 60947-2: 6 kA, Switchgear for DC applications

Categories:

  • Circuit breakers and fuses > Miniature circuit breaker (MCB)
  • EATON - MOELLER > Modular Switchgear – Industrial

Brand new product in its original packaging covered by the warranties and certifications provided by EATON - MOELLER

  • More Info
  • ETIM
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 131,00 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 5 days.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

General specifications

Product Name
Eaton Moeller series xPole - PLS6-DC MCB
Catalog Number
243136
Model Code
PLS6-C20/2-DC-MW
EAN
4015082431365
Product Length/Depth
85 mm
Product Height
73 mm
Product Width
35 mm
Product Weight
0.24 kg
Compliances
RoHS conform
Certifications
CE

Delivery program

Application
Switchgear for DC applications
Number of poles
Two-pole
Number of poles (total)
2
Number of poles (protected)
2
Tripping characteristic
C
Release characteristic
C
Amperage Rating
20 A
Type

Technical data - electrical

Voltage type
DC
Rated operational voltage (Ue) - max
220 V
Rated insulation voltage (Ui)
440 V
Rated impulse withstand voltage (Uimp)
4 kV
Frequency rating - min
0 Hz
Frequency rating - max
0 Hz
Rated switching capacity (IEC/EN 60947-2)
6 kA
Rated short-circuit breaking capacity (EN 60898) at 230 V
0 kA
Rated short-circuit breaking capacity (EN 60898) at 400 V
0 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 230 V
10 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 400 V
10 kA
Overvoltage category
III
Pollution degree
2

Technical data - mechanical

Width in number of modular spacings
2
Built-in depth
70.5 mm
Degree of protection
IP20
Connectable conductor cross section (multi-wired) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (solid-core) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
20 A
Heat dissipation per pole, current-dependent
0 W
Equipment heat dissipation, current-dependent
2.9 W
Static heat dissipation, non-current-dependent
0 W
Heat dissipation capacity
0 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
75 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Current limiting class
3
Features
Additional equipment possible
Special features
Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
Used with
Miniature circuit breaker
PLS6

ETIM for 243136 Circuit breakers and fuses (EC000042)

Feature nameBuilt-in depth (EF000218)
Feature value70.5 mm
Feature nameRelease characteristic (EF000889)
Feature valueC
Feature nameNumber of poles (total) (EF008618)
Feature value2
Feature nameNumber of protected poles (EF005548)
Feature value2
Feature nameRated current (EF000227)
Feature value20 A
Feature nameRated voltage (EF000228)
Feature value220 V
Feature nameRated insulation voltage Ui (EF001366)
Feature value440 V
Feature nameRated impulse withstand voltage Uimp (EF011980)
Feature value4 kV
Feature nameRated short-circuit breaking capacity Icn according to EN 60898 at 230 V (EF009556)
Feature value0 kA
Feature nameVoltage type (EF000187)
Feature valueDC
Feature nameRated short-circuit breaking capacity Icn according to EN 60898 at 400 V (EF009555)
Feature value0 kA
Feature nameRated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V (EF009557)
Feature value10 kA
Feature nameRated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V (EF009558)
Feature value10 kA
Feature nameFrequency (EF000416)
Feature value0 Hz
Feature namePower loss (EF005387)
Feature value5.8 W
Feature nameCurrent limiting class (EF002568)
Feature value3
Feature nameFlush-mounted installation (EF007517)
Feature valueNo
Feature nameConcurrently switching neutral conductor (EF005997)
Feature valueNo
Feature nameOver voltage category (EF002569)
Feature value3
Feature namePollution degree (EF002570)
Feature value2
Feature nameAdditional equipment possible (EF008148)
Feature valueYes
Feature nameWidth in number of modular spacings (EF002950)
Feature value2
Feature nameDegree of protection (IP) (EF005474)
Feature valueIP20
Feature nameAmbient temperature during operating (EF007515)
Feature value-25 °C
Feature nameConnectable conductor cross section multi-wired (EF007343)
Feature value1 mm²
Feature nameConnectable conductor cross section solid-core (EF007337)
Feature value1 mm²
Feature nameExplosion-proof (EF004663)
Feature valueNo

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.