— Niko 7/23/17, 11:04 AM
Total disaster
Overlate delivery, waited for 18 days, customer support 0, no mail answer, no phone answer in contac center, will never use this company again.

Images are for illustrative purposes only. Please refer to data sheet for details.
Reference: IB IL TEMP 2 RTD-PAC
Code: 2861328
Manufacturer: PHOENIX CONTACT
Description:
Categories:
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT
LAST VIEWED
| Orderkey | 2861328 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 165 (C-6-2017) |
| GTIN | 4017918894269 |
| Weight per Piece (excluding packing) | 67.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| 80 kPa ... 106 kPa (up to 3000 m above sea level, in ATEX Zone 2) | |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
| Mounting type | DIN rail |
|---|---|
| Net weight | 67 g |
| Note on weight specifications | with connector |
| Operating mode | Process data operation with 2 words |
| Diagnostics messages | Failure of the internal I/O supply I/O error message sent to the bus coupler |
| Failure of or insufficient communications power ULI/O error message sent to the bus coupler | |
| Peripheral fault Error message in the process data | |
| User error Error message in the process data |
| Designation | Inline local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
| Designation | Communications power (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current consumption | typ. 43 mA |
| max. 60 mA | |
| Designation | Supply of analog modules (UANA) |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 11 mA |
| max. 18 mA | |
| Power consumption | typ. 587 mW |
| Number of inputs | 2 |
|---|---|
| Input name | Analog RTD inputs |
| Description of the input | Input for resistive temperature sensors |
| Connection method | Spring-cage connection |
| Connection technology | 2, 3, 4-wire |
| Note regarding the connection technology | shielded |
| Sensor types (RTD) that can be used | Pt, Ni, KTY, Cu sensors, linear resistors |
| Linear resistance measuring range | 0 Ω ... 400 Ω |
| 0 Ω ... 4 kΩ | |
| Measuring principle | Successive approximation |
| Measured value representation | 16 bit two's complement |
| A/D conversion time | typ. 120 µs (per channel) |
| Resolution A/D | 16 bit |
| Process data update | 32 ms (both channels with 3-wire technology) |
| Test section | 7.5 V supply (bus logics)/24 V analog supply (analog I/O) 500 V AC 50 Hz 1 min. |
|---|---|
| 7.5 V supply (bus logics) / functional earth ground 500 V AC 50 Hz 1 min. | |
| 24 V analog supply (analog I/O) / functional earth ground 500 V AC 50 Hz 1 min. |
| Connection in acc. with standard | CUL |
|---|---|
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |
— Niko 7/23/17, 11:04 AM
Overlate delivery, waited for 18 days, customer support 0, no mail answer, no phone answer in contac center, will never use this company again.
— R Niko 7/18/17, 12:29 PM
Late delivery after 18 days (2-3 days specified on web site), not possible to reach a call center, was trying for 3 days; no answer from info@.. e mail, sorry first answer after my five e mails just to tell me that is not possible to return a package without penalty etc... all together a catastrophe
— R Niko 7/7/17, 12:26 PM
Order and pay product 5 days ago. Also pay for fast delivery over DHL air. I try to reach company over e mail still no normal answer, only automatic response. I try to reach company calling on europe number, no answer whole morning..
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.
5/5 .
— CHE 5/6/26, 10:33 AM
Product:MTZ18-4VM DANFOSS REFRIGERATION Reciproc...
5/5 merci beaucoup
— sotitradim 11/29/25, 11:12 AM
Product:SL20,MNM,IP42,300lm,1H SL2MNM42H1C EATON...
4/5 a,azing to use it
— B rahul 10/4/25, 8:05 AM
Product:661601 LEGRAND URA21LED 70LM 1H IP42 NP
4/5 Amazing to use it
— B rahul 10/4/25, 8:04 AM
Product:661601 LEGRAND URA21LED 70LM 1H IP42 NP