EATON - MOELLER CLS6-C40-DE 247617 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

CLS6-C40-DE 247617 EATON ELECTRIC Miniature circuit breaker (MCB), 40A, 1p, type C characteristic

Reference: CLS6-C40-DE

Code: 247617

Manufacturer: EATON - MOELLER

Description:

Miniature circuit breaker (MCB), 40A, 1p, type C characteristic
High quality miniature circuit breaker, contact position indicator red - green, comprehensive range of accessories suitable for subsequent installation, rated operational currents up to 63 A, tripping characteristics B, C, D, rated switching capacity 6 kA, Switchgear for residential and commercial applications

Categories:

  • Circuit breakers and fuses > Miniature circuit breaker (MCB)
  • EATON - MOELLER > Home Switchgear

Brand new product in its original packaging covered by the warranties and certifications provided by EATON - MOELLER

  • More Info
  • ETIM
  • PDF
  • Reviews
Guarantee, repair and return.

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

LAST VIEWED

MORE INFO

Miniature circuit breaker (MCB), 40A, 1p, type C characteristic
[

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
40 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Equipment heat dissipation, current-dependent [Pvid]
3.4 W
Static heat dissipation, non-current-dependent [Pvs]
0 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+55 °C
linear, per +1 °C, results in a 0.5% reduction of current carrying capacity
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
,

Technical data ETIM 7.0

Circuit breakers and fuses (EG000020) / Miniature circuit breaker (MCB) (EC000042)
Electric engineering, automation, process control engineering / Electrical installation, device / Miniature circuit breaker system (MCB) / Miniature circuit breaker (MCB) (ecl@ss10.0.1-27-14-19-01 [AAB905014])
Release characteristic
C
Number of poles (total)
1
Number of protected poles
1
Rated current
40 A
Rated voltage
230 V
Rated insulation voltage Ui
440 V
Rated impulse withstand voltage Uimp
4 kV
Rated short-circuit breaking capacity Icn EN 60898 at 230 V
6 kA
Rated short-circuit breaking capacity Icn EN 60898 at 400 V
6 kA
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V
0 kA
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V
0 kA
Voltage type
AC
Frequency
50 - 60 Hz
Current limiting class
3
Suitable for flush-mounted installation
No
Concurrently switching N-neutral
No
Over voltage category
3
Pollution degree
2
Additional equipment possible
Yes
Width in number of modular spacings
1
Built-in depth
70.5 mm
Degree of protection (IP)
IP20
Ambient temperature during operating
-25 - 55 °C
Connectable conductor cross section multi-wired
1 - 25 mm²
Connectable conductor cross section solid-core
1 - 25 mm²
]

ETIM for 247617 Circuit breakers and fuses (EC000042)

Feature nameBuilt-in depth (EF000218)
Feature value70.5 mm
Feature nameRelease characteristic (EF000889)
Feature valueC
Feature nameNumber of poles (total) (EF008618)
Feature value1
Feature nameNumber of protected poles (EF005548)
Feature value1
Feature nameRated current (EF000227)
Feature value40 A
Feature nameRated voltage (EF000228)
Feature value230 V
Feature nameRated insulation voltage Ui (EF001366)
Feature value440 V
Feature nameRated impulse withstand voltage Uimp (EF011980)
Feature value4 kV
Feature nameRated short-circuit breaking capacity Icn according to EN 60898 at 230 V (EF009556)
Feature value6 kA
Feature nameVoltage type (EF000187)
Feature valueAC
Feature nameRated short-circuit breaking capacity Icn according to EN 60898 at 400 V (EF009555)
Feature value6 kA
Feature nameRated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V (EF009557)
Feature value0 kA
Feature nameRated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V (EF009558)
Feature value0 kA
Feature nameFrequency (EF000416)
Feature value50 Hz
Feature nameCurrent limiting class (EF002568)
Feature value3
Feature nameFlush-mounted installation (EF007517)
Feature valueNo
Feature nameConcurrently switching neutral conductor (EF005997)
Feature valueNo
Feature nameOver voltage category (EF002569)
Feature value3
Feature namePollution degree (EF002570)
Feature value2
Feature nameAdditional equipment possible (EF008148)
Feature valueYes
Feature nameWidth in number of modular spacings (EF002950)
Feature value1
Feature nameDegree of protection (IP) (EF005474)
Feature valueIP20
Feature nameAmbient temperature during operating (EF007515)
Feature value-25 °C
Feature nameConnectable conductor cross section multi-wired (EF007343)
Feature value1 mm²
Feature nameConnectable conductor cross section solid-core (EF007337)
Feature value1 mm²
Feature nameExplosion-proof (EF004663)
Feature valueNo

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.